PROGRAMMING THE BATTERY CHARGER
GB
The devices belonging to one group " ", " " or " " can only dialog between themselves.
Group " " (Universal) is an exception as this can dialog with any other device.
The distinction between different groups is very important in order to connect all the devices to the same CAN
network even if they belong to different electrical systems.
The letter " " , " " or " ", will appear fl ashing on the display according to the current setting.
To change the setting, press and release the button quickly (press and release the button in less than 1 second).
To make the setting operative press the button for at least 2 seconds. The display will confi rm the setting by
showing the letter selected for one second (steady).
SELECTING GROUP ORDER OF PRIORITY
This function is used to determine the priority level of the battery charger within the network group.
This function is not currently preset in SBC ADV PLUS Medium Power series battery chargers. Setting value " "
is recommended.
The number " " , " " or " " will appear flashing on the display according to the current setting.
To change the setting press and release the button quickly (press and release the button in less than 1 second).
To make the setting operative press the button for at least 2 seconds. The display will confi rm the setting by
showing the number selected for one second (steady).
ACTIVATING/DEACTIVATING THE MONITOR MODE
This function enables the user to activate or deactivate the battery charger's "monitor" mode.
If it is activated, the "monitor" mode enables the battery charger to transmit and receive data on the CAN
network even if no AC power is being delivered. To do this, the battery charger is supplied with power from the
group of batteries using the master output. The current absorption, with "monitor" mode active, is less than
75mA (120mA for 24V models).
The battery charger exits "monitor" mode (is turned off) if the voltage of the master group of batteries is less
than 7Vdc (14Vdc for the 24V models).
This mode should be activated when the remote terminals are connected to the CAN network.
The letter " " (monitor mode Off) or " " (monitor mode On [Stand-by]), will appear fl ashing on the display
according to the current setting.
To change the setting press and release the button quickly (press and release in less than 1 second).
To make the setting operative press the button for at least 2 seconds. The display will confi rm the setting by
showing the letter selected for one second (steady).
Once the programming procedure has been completed, the following symbol will be shown for 1 second: " ".
22
SBC ADVANCED PLUS MEDIUM - REV005A