Resumen de contenidos para Ferroli ATLAS D 50 UNIT
Página 1
ATLAS D 50 UNIT IT - ISTRUZIONE PER L’USO L'INSTALLAZIONE E LA MANUTENZIONE ES - INSTRUCCIONES DE USO, INSTALACIÓN Y MANTENIMIENTO TR - KULLANMA, KURULUM VE BAK M TALIMATLAR EN - INSTRUCTIONS FOR USE, INSTALLATION AND MAINTENANCE FR - INSTRUCTIONS D'UTILISATION, D'INSTALLATION ET D'ENTRETIEN...
ATLAS D 50 UNIT è un generatore di calore ad alto rendimento, per la produzione di acqua calda sanitaria (opzionale) e per il riscaldamento, dotato di bruciatore soffiato a gasolio.
Página 3
ATLAS D 50 UNIT Accensione caldaia Regolazione temperatura sanitario • Aprire le valvole di intercettazione combustibile. Agire sui tasti sanitario +/- (part. 1 e 2 - fig. 1) per variare la temperatura da un minimo • Fornire alimentazione elettrica all'apparecchio.
ATLAS D 50 UNIT Se la temperatura ambiente risulta inferiore al valore desiderato si consiglia di impostare 3. INSTALLAZIONE una curva di ordine superiore e viceversa. Procedere con incrementi o diminuzioni di una 3.1 Disposizioni generali unità e verificare il risultato in ambiente.
16 (pompe e valvole di non ritorno devono essere fornite a parte). Effettuare: collegamenti elettrici come indicato nello schema elettrico al cap. 5.4. E' ne- cessario l'utilizzo di una sonda FERROLI. Il sistema di controllo caldaia, alla successiva accensione, riconosce la presenza della sonda bollitore e si configura automaticamente, attivando display e controlli relativi la funzione sanitario.
Far verificare da personale professio- nalmente qualificato l’efficienza e l’adeguatezza dell’impianto di terra, il costrut- FERROLI declina ogni responsabilità per danni a cose e/o persone derivanti dalla ma- tore non è responsabile per eventuali danni causati dalla mancanza di messa nomissione dell’apparecchio da parte di persone non qualificate e non autorizzate.
Página 7
ATLAS D 50 UNIT Regolazione pressione pompa Testa e serranda aria La pressione della pompa viene tarata in fabbrica per un funzionamento ottimale e di Regolare la testa e la portata aria in funzione della potenza del bruciatore come indicato norma non dovrebbe essere modificata.
ATLAS D 50 UNIT 4.2 Messa in servizio Verifiche durante il funzionamento Verifiche da eseguire alla prima accensione, e dopo tutte le operazioni di ma- • Accendere l’apparecchio come descritto nella sez. 2.3. nutenzione che abbiano comportato la disconnessione dagli impianti o un inter- •...
ATLAS D 50 UNIT 4.4 Risoluzione dei problemi Codice Anomalia Possibile causa Soluzione anomalia Diagnostica Sonda danneggiata o corto circuito Verificare il cablaggio o sostituire il La caldaia è dotata di un avanzato sistema di autodiagnosi. Nel caso di un’anomalia alla...
ATLAS D 50 UNIT 5. CARATTERISTICHE E DATI TECNICI 5.1 Dimensioni, attacchi e componenti principali fig. 32 - Dimensionale attacchi e componenti principali fig. 34 Mandata impianto 3/4” Ritorno impianto 1” Valvola di sicurezza riscaldamento Sfiato aria automatico Trasduttore di pressione...
ATLAS D 50 UNIT 5.2 Perdita di carico 5.3 Tabella dati tecnici Perdita di carico lato acqua Dato Unità ATLAS D 50 UNIT Numero elementi n° Portata termica max Hs = 56.6 / Hi = 53.2 Portata termica min Hs = 33.4 / Hi = 31.5...
Página 12
ATLAS D 50 UNIT cod. 3541I330 - Rev. 02 - 04/2018...
ATLAS D 50 UNIT 5.4 Schema elettrico Schema elettrico T° T° DBM06E DSP05 fig. 36 - Schema elettrico Circolatore riscaldamento Sonda temperatura acqua sanitaria (opzionale) Termoststo ambiente (opzionale) Circolatore bollitore (opzionale) Sonda esterna (opzionale) Cronocomando remoto (opzionale) Trasduttore di pressione Sensore doppio (Sicurezza + riscaldamento) Trasformatore d’accensione...
Página 14
C e r t i f i c a t o d i G a ra n z i a La presente garanzia convenzionale è valida per gli apparecchi È FERROLI S.p.A. - Via Ritonda 78/a - 37047 San Bonifacio (Verona) Italy - tel. +39.045.6139411 - fax. +39.045.6100933 - www.ferroli.com...
ATLAS D 50 UNIT es un generador de calor de alto rendimiento, para producción de agua caliente sanitaria (opcional) y calefacción, equipado con quemador soplado de ga- sóleo.
Página 16
ATLAS D 50 UNIT Encendido de la caldera Regulación de la temperatura del agua sanitaria • Abrir las válvulas de interceptación combustible. Mediante las teclas +/- (1 y 2 - fig. 1) se puede regular la temperatura del agua sanitaria •...
ATLAS D 50 UNIT Si la temperatura ambiente es inferior al valor deseado , se aconseja seleccionar una 3. INSTALACIÓN DEL APARATO curva de orden superior, y viceversa. Probar con aumentos o disminuciones de una uni- 3.1 Disposiciones generales dad y controlar el resultado en el ambiente.
5.4. Es nece- sario utilizar una sonda FERROLI. Cuando se enciende la caldera, el sistema de control reconoce la sonda del acumulador y se configura automáticamente, activando la panta- lla y los controles de la función de agua sanitaria.
Solicitar a personal profesionalmente cualificado que controle la eficacia FERROLI declina toda responsabilidad por daños materiales o personales derivados de y la adecuación de la instalación de tierra ya que el fabricante no se hace res- la manipulación del aparato por personas que no estén debidamente autorizadas.
Página 20
ATLAS D 50 UNIT Regulación de la presión de la bomba Cabeza y compuerta de aire La presión de la bomba se regula en fábrica para un funcionamiento optimizado, y nor- Regule la cabeza y el caudal del aire en función de la potencia del quemador, como se malmente no debería modificarse.
ATLAS D 50 UNIT 4.2 Puesta en servicio Controles a efectuar durante el funcionamiento Controles que se han de efectuar durante el primer encendido, tras las opera- • Encender el aparato tal como se indica en la sec. 2.3. ciones de mantenimiento que exijan desconectar la caldera y después de cual- •...
ATLAS D 50 UNIT 4.4 Solución de problemas Código Anomalía Causa posible Solución Diagnóstico anomalía La caldera está dotada de un avanzado sistema de autodiagnóstico. Si se presenta una Sonda averiada o cableado en cortocir- Controlar el cableado o cambiar el anomalía en la caldera, la pantalla parpadea junto con el símbolo de fallo (22 - fig.
ATLAS D 50 UNIT 5. CARACTERÍSTICAS Y DATOS TÉCNICOS 5.1 Dimensiones, conexiones y componentes principales fig. 34 Ida a calefacción 3/4" fig. 32 - Dimensiones de conexiones y componentes principales Retorno de calefacción 1" Válvula de seguridad calefacción Purgador de aire automático Transductor de presión...
ATLAS D 50 UNIT 5.2 Pérdida de carga 5.3 Tabla de datos técnicos Pérdida de carga lado agua Dato Unidad ATLAS D 50 UNIT Número elementos nº Capacidad térmica máxima Hs = 56.6 / Hi = 53.2 Capacidad térmica mínima Hs = 33.4 / Hi = 31.5...
Página 25
ATLAS D 50 UNIT cod. 3541I330 - Rev. 02 - 04/2018...
ATLAS D 50 UNIT 5.4 Esquema eléctrico Esquema eléctrico T° T° DBM06E DSP05 fig. 36 - Esquema eléctrico Circulador de calefacción Sonda de temperatura AS (opcional) Termostato de ambiente (opcional) Circulador de AS (opcional) Sonda exterior (opcional) Cronomando remoto (opcional) Transductor de presión...
önemli bilgiler vermektedir. ATLAS D 50 UNIT s v yak tla (mazot) çal an brülörler ile donat lm , s cak su üretimi (opsiyonel) veya s tma amaçl kullan lan yüksek performansl bir s üretecidir. Kombinin gövdesi, çelik man on ve gergilerle ba lant l dökme demirden yap lm t r.
Página 29
ATLAS D 50 UNIT Kombinin yak lmas S cak musluk suyu s cakl ayar • Yak t açma-kapama valf n aç n z. S cakl minimum 10°C ile maksimum 65°C aras nda ayarlamak için s cak musluk suyu • Cihaz n elektrik beslemesini aç n z.
ATLAS D 50 UNIT E er ortam s cakl istenilen de erin alt na dü erse, daha yüksek dereceden bir e ri 3. KURULUM ayarlanmas veya tersi durumda bunun tersinin uygulanmas tavsiye edilir. Bir derece 3.1 Genel talimatlar artt rma veya azaltma yap n z ve ortamdaki de i ikli i kontrol ediniz.
Página 31
(pompalar ve geri-dönü valflar ayr ca tedarik edilmelidir). A a dakiler gerçekle tiriniz: k sm ndaki elektrik emas nda gösterilen elektrik ba lant lar cap. 5.4. Bir FERROLI sen- sörünün kullan lmas gereklidir. Kombi kontrol sistemi, bir sonraki çal t rmada s t c ka- zan sensörünü...
Página 32
Mesleki aç dan kalifiye bir personele, topraklama sisteminin veri- mlili ini ve de uygunlu unu kontrol ettiriniz; imalatç , topraklama sistemindeki FERROLI cihaz n yetkisiz ki iler taraf ndan kurcalanmas ndan kaynaklanan, insanlara ar za nedeniyle meydana gelecek hasarlardan dolay sorumlu olmayacakt r.
Página 33
ATLAS D 50 UNIT Pompa bas nc ayar Hava kapak ve ba l Pompan n bas nc , optimum i letim (çal ma) için fabrikada ayarlanm olup, normalde Hava kafas n /ba l n ve ç k n , belirtilmekte olan brülörün çal mas na göre ayar- de i tirilmemesi gerekmektedir.
Página 34
ATLAS D 50 UNIT 4.2 Servise alma letim an ndaki kontroller lk çal t rma an nda ve sistemlerden ayr lmas n gerektiren i lemlerden veya • Cihaz sez. 2.3'de belirtildi i gibi çal t r n z. emniyet cihazlar nda ya da kombinin di er aksamlar nda gerçekle tirilen •...
ATLAS D 50 UNIT 4.4 Sorunlar n giderilmesi Ar za Ar za Olas neden Çözüm kodu Ar za te his Sensör hasarl veya kablo ba lant lar nda Sensörün kablo tesisat n kontrol Kombi, ileri seviye bir otomatik-ar za te his sistemi ile donat lm t r. Kombide bir ar za k sa-devre edin veya sensörü...
Página 36
ATLAS D 50 UNIT 5. TEKNIK ÖZELLIKLER VE VERILER 5.1 Boyutlar, ba lant lar ve ana bile enler ek. 34 Sistem ç k 3/4” ek. 32 - Ba lant boyutlar ve ana bile enler Sistem giri i 1” Is tma emniyet valf Otomatik hava tahliyesi Bas nç...
Página 37
ATLAS D 50 UNIT 5.2 Yük kayb 5.3 Teknik veriler tablosu Su k sm yük kayb Veri Birim ATLAS D 50 UNIT Elemanlar n say s n° Maks. termik kapasite Hs = 56.6 / Hi = 53.2 Min. termik kapasite Hs = 33.4 / Hi = 31.5...
Página 38
ATLAS D 50 UNIT 5.4 Elektrik emas Elektrik emas T° T° DBM06E DSP05 ek. 36 - Elektrik emas Is tma sirkülatörü S cak su s sensörü (opsiyonel) Ortam termostat (opsiyonel) S hhi su sirkülatörü (opsiyonel) Harici sensör (opsiyonel) Uzaktan zamanlay c kontrolü (opsiyonel) Bas nç...
Please read this manual carefully since it provides important information on safe installation, use and maintenance. ATLAS D 50 UNIT is a high-efficiency heat generator for domestic hot water production (optional) and heating, equipped with a blown oil burner. The boiler shell consists of cast- iron elements, assembled with double cones and steel stays.
Página 40
ATLAS D 50 UNIT Boiler lighting DHW temperature adjustment • Open the fuel on-off valves. Use the DHW buttons +/- (details 1 and 2 - fig. 1) to adjust the temperature from a min. • Switch on the power to the unit.
ATLAS D 50 UNIT If the room temperature is lower than the required value, it is advisable to set a higher 3. INSTALLATION order curve and vice versa. Proceed by increasing or decreasing in steps of one and 3.1 General Instructions check the result in the room.
ATLAS D 50 UNIT Connection to a storage tank for domestic hot water production The unit's electronic board is arranged for managing an external storage tank for domes- tic hot water production. Carry out the plumbing connections according to the diagram fig.
The manufacturer is not responsible for any damage FERROLI declines any liability for damage and/or injury caused by unqualified and un- caused by failure to earth the system. Also make sure that the electrical system authorised persons tampering with the unit.
Página 44
ATLAS D 50 UNIT Pump pressure adjustment Head and air lock The pump pressure is factory set for optimum operation and should not normally be Adjust the head and air flow rate according to the burner power as given in fig. 26 changed.
Página 45
ATLAS D 50 UNIT 4.2 Commissioning Checks during operation Checks to be done at first lighting, and after all maintenance operations that in- • Ignite the appliance as described in sec. 2.3. volved disconnection from the systems or work on safety devices or parts of the •...
ATLAS D 50 UNIT 4.4 Troubleshooting Fault Fault Possible cause Cure Diagnostics code The boiler is equipped with an advanced self-diagnosis system. In case of a boiler fault, Pressure too low Fill the system Incorrect system water pres- the display will flash together with the fault symbol (detail 22 - fig. 1) indicating the fault...
ATLAS D 50 UNIT 5. TECHNICAL DATA AND CHARACTERISTICS 5.1 Dimensions, connections and main components fig. 34 fig. 32 - Dimensions, connections and main components System delivery 3/4” System return 1” Heating safety valve Automatic air vent Pressure transducer Double sensor (Heating + Safety)
ATLAS D 50 UNIT 5.2 Loss of head 5.3 Technical data table Pressure loss water side Data Unit ATLAS D 50 UNIT Number of elements Max. heating capacity Hs = 56.6 / Hi = 53.2 Min. heating capacity Hs = 33.4 / Hi = 31.5 Max.
Página 49
ATLAS D 50 UNIT cod. 3541I330 - Rev. 02 - 04/2018...
ATLAS D 50 UNIT est un générateur de chaleur à haut rendement pour la production d'eau chaude sanitaire (option) et de chauffage, équipé d'un brûleur soufflé à gazole. Le corps de la chaudière se compose d'éléments en fonte, assemblés à...
Página 52
ATLAS D 50 UNIT Allumage de la chaudière Réglage de la température de l'eau chaude sanitaire • Ouvrir les vannes d'arrêt du combustible. Pour régler la température entre 10 °C (minimum) et 65 °C (maximum), agir sur les tou- •...
ATLAS D 50 UNIT Si la température ambiante est inférieure à la valeur désirée, il est conseillé de définir 3. INSTALLATION une courbe supérieure et vice versa. Augmenter ou diminuer d'une unité et vérifier le ré- 3.1 Dispositions générales sultat dans la pièce ou le local.
ATLAS D 50 UNIT Raccordement à un ballon servant à la production d'eau chaude sanitaire La carte électronique de l'appareil est conçue pour la gestion d'un ballon externe pour la production d'eau chaude sanitaire. Effectuer les raccordements hydrauliques selon le schéma fig.
à un dispositif de mise à la terre efficace conformément aux normes électriques en vigueur. Faire vérifier par un professionnel qualifié FERROLI Toute responsabilité contractuelle et extracontractuelle du constructeur est l'efficacité et la conformité du dispositif de mise à la terre. Le constructeur ne exclue pour les dommages causés par des erreurs dans l'installation et l'utilisation et,...
Página 56
ATLAS D 50 UNIT Réglage de la pression de la pompe Tête et registre d'air La pression de la pompe est réglée en usine pour un fonctionnement optimal. En règle Régler la tête et le débit de l'air en fonction de la puissance du brûleur comme indiqué...
ATLAS D 50 UNIT 4.2 Mise en service Vérifications en cours de fonctionnement Vérifications à effectuer au premier allumage et après toutes les opérations • Allumer l’appareil comme indiqué dans la sez. 2.3. d'entretien ayant occasionné le débranchement des installations ou une inter- •...
ATLAS D 50 UNIT 4.4 Dépannage Code Anomalie Causes probables Solution anomalie Diagnostic Pression trop basse Remplir l'installation Pression eau installa- La chaudière est équipée d'un dispositif d'autodiagnostic avancé. En cas d'anomalies de tion incorrecte fonctionnement de la chaudière, l'affichage clignote avec le symbole d'anomalie (rep. 22 Capteur endommagé...
ATLAS D 50 UNIT 5.2 Perte de charge 5.3 Tableau des caractéristiques techniques Perte de charge côté eau Donnée Unité ATLAS D 50 UNIT Nombre d'éléments nbre Puissance thermique maxi Hs = 56.6 / Hi = 53.2 Puissance thermique mini Hs = 33.4 / Hi = 31.5...
Página 61
ATLAS D 50 UNIT cod. 3541I330 - Rev. 02 - 04/2018...
αφορο ν την ασφαλ εγκατ σταση, χρ ση και συντ ρηση. Οι ενδε ξεις διαβ θμισης του νερο οικιακ ς χρ σης (λεπτ. 11 - fig. 1) αν βουν διαδο ATLAS D 50 UNIT ε ναι μια γενν τρια θερμ τητας υψηλ ς απ δοσης, για την παραγωγ χικ...
Página 64
ATLAS D 50 UNIT Ενεργοπο ηση λ βητα Ρ θμιση θερμοκρασ ας νερο οικιακ ς χρ σης • Ανο ξτε τις βαλβ δες διακοπ ς παροχ ς καυσ μου. Πατ στε τα κουμπι νερο οικιακ ς χρ σης +/- (λεπτ. 1 και 2 - fig. 1) για να ρυθμ σετε...
ATLAS D 50 UNIT Ε ν η θερμοκρασ α περιβ λλοντος ε ναι χαμηλ τερη απ την επιθυμητ , συνιστ ται η 3. ΕΓΚΑΤ ΣΤΑΣΗ ρ θμιση καμπ λης αν τερης τ ξης και αντ στροφα. Αυξ στε μει στε την τιμ κατ...
Página 66
Εκτελ στε: τις ηλεκτρικ ς συνδ σεις σ μφωνα με το σχεδι γραμμα στην cap. 5.4. Ε ναι αναγκα α η χρ ση εν ς ανιχνευτ FERROLI. Στο επ μενο ναμμα το σ στημα ελ γχου του λ βητα αναγνωρ ζει την παρουσ α του ανιχνευτ θερμαντ ρα και διαμορφ νεται...
Página 67
στασης γε ωσης. Ο κατασκευαστ ς δεν φ ρει καμ α ευθ νη για ενδεχ μενες FERROLI δεν φ ρει καμ α ευθ νη για υλικ ς ζημι ς /και τραυματισμο ς που οφε λον βλ βες που οφε λονται στην λλειψη γε ωσης της εγκατ στασης. Βεβαιωθε τε...
Página 68
ATLAS D 50 UNIT Ρ θμιση π εσης αντλ ας Κεφαλ και τ μπερ α ρα Η π εση της αντλ ας ρυθμ ζεται εργοστασιακ για β λτιστη λειτουργ α και, κατ καν Ρυθμ στε την κεφαλ και την παροχ α ρα αν λογα με την ισχ του καυστ ρα, πως...
Página 69
ATLAS D 50 UNIT 4.2 Λειτουργ α λεγχοι κατ τη δι ρκεια της λειτουργ ας λεγχοι που πρ πει να εκτελο νται κατ την πρ τη ενεργοπο ηση, καθ ς και • Αν ψτε τη συσκευ σ μφωνα με τις οδηγ ες στην sez. 2.3.
Página 70
ATLAS D 50 UNIT 4.4 Επ λυση προβλημ των Κωδικüς δυσλει Δυσλειτουργßα ΠιθανÞ αιτßα Λýση Δι γνωση τουργßας Ο λ βητας διαθ τει προηγμ νο σ στημα αυτοδι γνωσης. Σε περ πτωση δυσλειτουργ ας ΕλÝγξτε και τροποποιÞστε, εÜν του λ βητα, η οθ νη αναβοσβ νει μαζ με το σ μβολο δυσλειτουργ ας (λεπτ. 22 - fig. 1) ΑκατÜλληλες...
Página 71
ATLAS D 50 UNIT 5. ΤΕΧΝΙΚ ΧΑΡΑΚΤΗΡΙΣΤΙΚ ΚΑΙ ΣΤΟΙΧΕ Α 5.1 Διαστ σεις, συνδ σεις και κ ρια εξαρτ ματα . 34 Παροχ εγκατ στασης 3/4” . 32 - Διαστ σεις, συνδ σεις και κ ρια εξαρτ ματα Επιστροφ εγκατ στασης 1”...
Página 72
ATLAS D 50 UNIT 5.2 Πτ ση π εσης 5.3 Π νακας τεχνικ ν στοιχε ων Πτ ση π εσης στην πλευρ νερο Στοιχεßο ΜονÜδα ATLAS D 50 UNIT Αριθμüς στοιχεßων αρ. ΜÝγιστη θερμικÞ παροχÞ Hs = 56.6 / Hi = 53.2 ΕλÜχιστη...
Página 73
ATLAS D 50 UNIT cod. 3541I330 - Rev. 02 - 04/2018...
2.1 Presentatie fig. 2 Geachte klant, Wij danken u dat uw keus is gevallen op een verwarmingsketel FERROLI met geavan- Sanitair water (Comfort) ceerd concept en vooruitstrevende technologie, een uiterst betrouwbare constructie van Het verzoek om sanitair water (naar aanleiding van gebruik van warm sanitair water) hoogstaande kwaliteit.
Página 76
ATLAS D 50 UNIT Aanzetten verwarmingsketel Regeling van temperatuur sanitair water • Maak de brandstofkleppen open. +/- Bedien de toetsen voor sanitair water (detail 1 en 2 - fig. 1) om de temperatuur te • Schakel de stroom naar het apparaat in.
ATLAS D 50 UNIT Als de omgevingstemperatuur lager blijkt dan de gewenste waarde wordt aanbevolen 3. INSTALLATIE een hogere curve in te stellen en omgekeerd. Verhoog of verlaag de curve met één 3.1 Algemene regels eenheid en verifieer daarna de omgevingstemperatuur.
ATLAS D 50 UNIT Aansluiten van een boiler voor sanitair warm water De elektronische kaart van het apparaat biedt de mogelijkheid voor het beheren van een externe boiler voor de productie van sanitair warm water. Maak de hydraulische aanslu- itingen volgens schema fig. 16 (pompen en terugslagkleppen dienen apart te worden besteld).
Laat bovendien controleren of de elektrische installatie geschikt is FERROLI is geenszins aansprakelijk voor schade aan zaken en/of persoonlijk letsel, ve- voor het maximumvermogen dat door het apparaat wordt opgenomen (dit staat roorzaakt door ingrepen op het apparaat, uitgevoerd door onbevoegde en ondeskundige vermeld op de typeplaat van de verwarmingsketel).
Página 80
ATLAS D 50 UNIT Regeling pompdruk Kop en luchtschuif Voor een optimale werking wordt de druk van de pomp in de fabriek afgesteld; dit dient Stel kop en luchttoevoer af op grond van het vermogen van de brander, zoals aangege- in de regel niet te worden gewijzigd.
ATLAS D 50 UNIT 4.2 Inwerkingstelling Controles tijdens de werking Controles die uitgevoerd moeten worden bij de eerste ontsteking en naar aan- • Schakel het apparaat in zoals beschreven in sez. 2.3. leiding van alle onderhoudswerkzaamheden die afsluiting van de installaties •...
ATLAS D 50 UNIT 4.4 Oplossen van storingen Code Storing Mogelijke oorzaak Oplossing storing Diagnostiek Sonde beschadigd of kortsluiting in bedra- Controleer de bedrading of vervang De verwarmingsketel is voorzien van een geavanceerd zelfdiagnosesysteem. Bij een ding de sensor storing in de verwarmingsketel knippert het display samen met het storingssymbool (de- Storing sonde buiten- tail 22 - fig.
ATLAS D 50 UNIT 5.2 Belastingverlies 5.3 Tabel technische gegevens Belastingsverlies waterzijde Gegeven Eenheid ATLAS D 50 UNIT Aantal elementen aantal Max. thermische opbrengst Hs = 56.6 / Hi = 53.2 Min. thermische opbrengst Hs = 33.4 / Hi = 31.5 Max.
Página 85
ATLAS D 50 UNIT 5.4 Schakelschema Schakelschema T° T° DBM06E DSP05 fig. 36 - Schakelschema Circulatiepomp verwarming Temperatuursonde sanitair water (optioneel) Omgevingsthermostaat (optioneel) Circolatiepomp sanitair water (optioneel) Externe sonde (optie) Klokthermostaat met afstandsbediening (optioneel) Drukomzetter Dubbele sensor (Beveiliging + verwarming)
Página 95
ATLAS D 50 UNIT ATLAS D 50 UNIT Hs = 56.6 / Hi = 53.2 Hs = 33.4 / Hi = 31.5 Pmax (80-60°C) % Hs = 88.3 / Hi = 94.0 % Hs = 91.4 / Hi = 97.3...
Página 96
ATLAS D 50 UNIT T° T° DBM06E DSP05 . 36 - cod. 3541I330 - Rev. 02 - 04/2018...
Página 97
LA MARCATURA CERTIFICA CHE I PRODOTTI SODDISFANO I REQUISITI FONDAMENTALI DELLE DIRETTIVE PERTINENTI IN VIGORE. LA DICHIARAZIONE DI CONFORMITÀ PUÒ ESSERE RICHIESTA AL PRODUTTORE. EL MARCADO CREDITA QUE LOS PRODUCTOS CUMPLEN LOS REQUISITOS FUNDAMENTALES DE LAS DIRECTIVAS APLICABLES. LA DECLARACIÓN DE CONFORMIDAD PUEDE SOLICITARSE AL FABRICANTE ARET ÜRÜNLER N YÜRÜRLÜKTE OLAN YÖNETMEL KLER N TEMEL GEREKL L KLER NE UYGUN OLDU UNU BELGELEMEKTED R.