CONsTaNT PrEssUrE OPEraTION
• Check that the transmitter output signal type jumper (mA/V) in the voltage position (factory
setting).
• Configure the DIP switches as indicated in the tables below. The required pressure range is
selected using the switches DIP1, DIP2 and DIP3.
Pressure range (Pa)
-50...+50
0...+100
0...+150
0...+300
0...+500
0...+1000
0...+1600
0...+2500
DIP switch DIP 4/5/6
DIP 4
DIP 5
DIP 6
6.7.2.2.2 TDP-D MODEl
DIP 1
1
0
1
0
1
0
1
0
ON / OFF
-
Select according to the required damping
OFF
52
DIP 2
1
1
0
0
1
1
0
0
Notes
Not used
time: 0,4s (OFF) / 10s (ON))
Minimum output voltage 0V
DIP 3
1
1
1
1
0
0
0
0