Electrical connection of the flame detector
It is important for signal transmission to be almost totally free of
any disturbances or loss:
•
always separate the detector cables from the other cables:
– Line capacitance reduces the magnitude of the flame signal.
– Use a separate cable.
Technical data
REC27 control box... Mains voltage
Mains frequency
Power absorption
Safety class
Load on
Main fuse of perm. network (external)
'input' terminals
F1 unit fuse (internal)
Main power supply: input current based on the operating status of the control box
Undervoltage
• Safety stop from the operating position to
the mains voltage
• Restart on the increase of the mains power
supply
Load on 'output'
Total load on the contacts:
terminals
• Mains voltage
• Input current (safety circuit):
- Fan motor contactor
- Ignition transformer
- Valve
- Oil pump / magnetic clutch
Load on a single contact:
Fan motor contact maker
•
•
•
Alarm exit
•
•
•
Ignition transformer
•
•
•
Fuel valves
•
•
•
Display operation
•
•
•
Cable lengths
Main line
Environmental
Operation
conditions
Climatic conditions
Mechanical conditions
Temperature range
Humidity
20040563
Technical description of the burner
Nominal voltage
Nominal current
Power factor
Nominal voltage
Nominal current
Power factor
Nominal voltage
Nominal current
Power factor
Nominal voltage
Nominal current
Power factor
Nominal voltage
Nominal current
Power factor
•
Respect the allowed cable lengths.
•
The ionisation probe is not protected against the risk of elec-
trocution. When connected to the electricity supply, the ionisa-
tion probe must be protected against any accidental contact.
•
The earthing of the burner must be in accordance with rele-
vant standards; earthing the boiler only is not sufficient.
AC 230V -15% / +10%
50 / 60 Hz ±6 %
< 30W (normal)
I, with components in compliance with II and III, according to
DIN EN 60730-1
Max. 16 AT
6.3 AT (DIN EN 60 127 2/5)
approx. AC 186V
approx. AC 195V
AC 230 V -15 % / +10 %
Max. 5 A
AC 230 V - 50 / 60 Hz
1A
cos > 0.4
AC 230 V - 50 / 60 Hz
1A
cos > 0.4
AC 230 V - 50 / 60 Hz
2A
cos > 0.2
AC 230 V - 50 / 60 Hz
2A
cos > 0.4
AC 230 V - 50 / 60 Hz
0.5A
cos > 0.4
Max. 100 m (100 pF/m)
DIN EN 60721-3-3
Classe 3K3
Classe 3M3
-20...+60°C
< 95% RH
14
GB
Tab. F