Rollerblind Powered
7.3
Notes on connecting to 230 Vw
Observe the following notes:
• All work on the electricity supply for the blind has to be carried out by a qualified
or competent person.
• The device shall be installed in accordance with national wiring regulations and
any other regulations in force, specific to the location of the installation, e. g.
marine application.
• Observe the cross section for cables:
– Motor cable: 4 core 0.5 mm
800 mm, due to cable not being a LSF (Low Smoke and Fume) variant
– Switch cable: 4 core min. 1.5 mm
– Infrastructure cable: Size is to be determined by a qualified electrician
• A ground connection to the housing of the switch is required to satisfy safety and
requirements of the Institution of Electrical Engineers (IEE).
7.4
Notes on connecting to AP Remote control
Refer to the AP Remote control manual for further instructions.
7.5
Fitting the blinds
A
NOTICE! Risk of damage
Consider using two people to install the product if the blind is large or
the installation location is difficult to reach alone.
➤ Proceed as shown:
– BR leaflet:
BR 38/46: fig. 2 to fig. 4
BR 55: fig. 5 to fig. 7
– MP leaflet: fig. 2 to fig. 3
– CA leaflet: fig. 2 to fig. 3
➤ Proceed as shown to remove the blinds:
– BR leaflet:
BR 38/46: fig. 8
BR 55: fig. 9
– MP leaflet: fig. 4
– CA leaflet: fig. 4
EN
2
(max. tail length for marine applications),
2
Installation
9