Start up
Description, settings
Combustion air
STA5
MV 2
MV 1
10
8
6
4
2 0
1. Stufe
2. Stufe
8
2 0
10
6
4
Power
Cam setting in °
st
d
Burner
1
st.
2
st.
1
kW
kW
cam IV
60
45
NC9
55
72
55
84
44
Servomotor Y10
1
Four red cams, of which 3 are
adjustable
2
Positioning mark to the cams
relative to the graduated cylinders 4
S
Cam adjusting screw
4
Two fixed cylinders graduated
from 0 to 18
5
Air flap positioning pointer
6
Plug-in electrical connector
Cam function
Cam
Function
S
Cam adjust screws
II
Power supply for the stage two
fuel valve (MV2)
III
Power supply for the stage one
fuel valve (MV1)
m
Cams II and III are coupled.
· Adjust them in-between the value
for cam IV and the value for cam
V.
IV
Stage one air flow rate.
V
Stage two air flow rate.
st
d
st.
2
st.
cam V
2
8
6
13
6
18
06/2004 - Art.Nr. 13 011 288C
Settings
· Remove the cover.
· Check cam drum reset.
· Preset cams according to boiler
capacity and values shown in the
table here below.
m
In order to do this:
· Adjust cam with screws S. The
angular position is found in relation
to each cam's index.
m
Servomotor adjust range: 160°
(between graduations 2 and 18).
Don't set the air flap below 20°
(graduation 2).