Installation and Operation Manual - SSW-05 Plus
Parameter
Description / Notes
P308
Network Address
P313
Action of the Serial
Communication
Verification
Values for P313:
1- It indicates only error.
2- Indicates error and disables the Soft-Starter by ramp. If the programmed deceleration
3- Indicates error and causes general disabling of the Soft-Starter. It can be used as emergency
4- Indicates error and program P264 with the value 1. The bit 0 of V03 is reseted.
P314
Verification Time of the
Serial Communication
P610
Immediate Undercurrent
P611
Immediate Undercurrent
Time
23. APPENDIX FOR CE CONFORMANCE:
The SSW-05 Plus, was tested to meet the following directives:
23.1. EMC and LVD Directives:
EMC Directive 89/336/EEC (Electromagnetic Compatibility), using a Technical Construction File
and the following standards:
EN60947-4-2: Low-voltage switchgear and controlgear Part 4, contactors and motor-starters
Section 2. AC semiconductor motor controllers and starters.
Low Voltage Directive (LVD) 73/23/EEC
Attention
The SSW-05 Plus line has been designed for class A equipment. Use of the products in
domestic environments may cause radio interference, in which case the user may be
required to employ additional mitigation methods.
Note
The conformity of the Soft-Starter to any standard does not guarantee that the entire
installation will conform.
Many other factors can influence the total installation. Only direct measurements can verify
total conformity.
Attention:
Never program this parameter with a current value that is not the exact value of
the SSW-05 Soft Starter Model you are using. Incorrect setup may damage the
SSW-05 Soft-Starter.
It defines the address at which the Soft-Starter will respond on the communication
network between all equipment connected to this network.
This parameter has the purpose to set the action to be taken when an error indication
occurs.
Note:
To attribute a function to this parameter, set P314 different from 0 = Off.
time is equal to 0 sec, the motor driven by the Soft-Starter will be stopped by inertia.
stopping.
This parameter has the function to enable or disable, as well as to set the verification
time of the serial communication. This protection acts when the serial communication
between the master and the Soft-Starter is interrupted generating the respective
indication or introducing an action as set at parameter P313.
Note:
Enable this function only if there is a cyclic serial communication with a master.
Set the verification time according to the time of the telegrams sent by the master.
The monitoring occurs only when the SSW-05 Plus reaches steady-state. (100% of
voltage).
This protection acts when the current that flows throught the SSW-05 is lower than P610%
of current set at trimpot motor current, for a time period longer than the value set in P611.
This function is helpful in applications with hydraulic pumps, which cannot operate at
no load.
This parameter sets the maximum time that the load can operate with undercurrent,
as adjusted in P610.
English-30