HANDLE (REMOVABLE) FOR
MANUALLY ROTATING SHAFT**
SCREWS (2)**
STEM ASSEMBLY COVER**
STEM ASSEMBLY**
SCREWS (2)**
VALVE STEMCOUPLER
VALVE BODY
**INCLUDED IN REPLACEMENT KIT (PART NO. 5112-11)
Fig. 3. Valve assembly exploded view.
Fig. 4. Vertical valve installation.
Mounting Plate Adjustment
The Actuator Mounting Plate can be rotated to a different
position for installation in confined spaces. This is
accomplished as follows:
BOLT**
ANTI-ROTATION
BRACKET**
MOUNTING
PLATE**
NOTE: Take note of the screw hole positions on the
WING NUT**
10. If desired, replace the handle on the shaft.
NOTE: See Fig. 3 for valve exploded view.
M13738A
Electrical Installation
M34954
3
VBN CONTROL BALL VALVES AND ACTUATORS
45
Fig. 5. Acceptable valve angle from vertical.
1. Remove the handle from the shaft and set it aside.
2. Remove the two screws that hold the stem assembly to
the mounting plate and set them aside.
3. Remove and set aside the stem assembly.
4. Remove and set aside the two screws that attach the
mounting plate to the valve.
5. Remove and set aside hold-down ring from mounting
plate.
6. Rotate mounting plate around valve top to the desired
position.
valve. They limit the mounting plate positions.
7. Lower ring down to valve body and engage it in the new
position relative to the mounting plate.
8. Tighten screws to valve body securing the mounting
plate.
9. Reattach the stem assembly to the mounting plate.
1. If necessary, remove actuator wiring cover.
2. Wire actuator using Figures 6 through 22 for the
application required.
3. Replace cover.
45
M33091
62-2025EFS—04