Service
Parameter
Menu item
Description
[EN]
[DE]
50
Set flush time.
[FlshTime]
Duration of the flush after one
[Spülzeit]
use
51
Set detection time.
[DetectT]
Minimum time within the
[VerweilZ]
detection range to be
recognised as a user
52
Set delay of follow-up flush.
[DelFollwF]
Is active when menu item 36
[FolgVerzö]
"Select follow-up flush" is
[ON] [EIN]
53
Set flush time – interval flush.
[IntFlushT]
Is active when the menu item
[IntervSpZ]
32 "Select interval flush" is
[ON] [EIN]
54
Set flush interval – interval flush.
[IntervalT]
Is active when the menu item
[IntervalZ]
32 "Select interval flush" is
[ON] [EIN]
55
Set cleaning time.
[CleanTime]
Defines the length of inactive
[ReiniZeit]
time of the flush control when
the menu item 25 [CleanMode]
[Reinigung] is started
56
Hybrid mode – set flush time. Is
[HybFlshT]
active when menu item 39
[HybFlshT]
"Activate hybrid mode" is [1] or
[2]
57
Hybrid mode – set time-out. Is
[HybTimOut]
active when menu item 39
[HybTimOut]
"Activate hybrid mode" is [1]
58
Hybrid mode – set interval. Is
[HybIntT]
active when menu item 39
[HybIntT]
"Activate hybrid mode" is [2]
59
Purging flush – set flush time. Is
[PurgFlshT]
active when menu item 40
[PurgFlshT]
"Activate purging flush" is
[ON] [EIN]
60
Purging flush – set interval. Is
[PurgIntT]
active when menu item 40
[PurgIntT]
"Activate purging flush" is
[ON] [EIN]
40
Application
Optimisation of flushing out the
urinal ceramic
Note water consumption
Preventing flushes due to
unintentional entry into the
detection range
–
–
–
–
–
–
–
–
–
Adjustment
Factory
range
setting
1–15 s [...]
7 s [7]
3–15 s [...]
7 s [7]
1–24 h [...]
2 h [2]
3–180 s [...]
5 s [5]
1–168 h [...]
24 h [24]
1–16 min [...]
10 min [10]
1–15 s [...]
7 s [7]
5–720 min [...]
60 min [60]
10–1440 min [...]
1440 min
[1440]
3–30 s [...]
12 s [12]
1–168 h [...]
6 h [6]