of the system. As soon as possible however, the failing safety devices must be repaired and
activated.
VISUAL AND SOUND ALARMS
BLINKER
Connect the flashing light to the blinker output. Use flashing lights (ACG7072) 40W maximum.
PRE-BLINKING
DIP 5 - OFF => motor and blinker start simultaneously.
DIP 5 - ON => blinker starts 3 seconds before the motor.
BUZZER
It has the task to signal the intervention of the security, the anomalies and the memorization
and cancellation of the radio codes.
SIGNAL - 24Vdc GATE OPEN WARNING LIGHT (COM A+/SIGNAL-)
Signals when the gate is open, partially open or not closed completely. It turns off only when
the gate is completely closed.
During opening, it flashes slowly.
When the gate is stationary or opened, it is permanently on.
During closing, it flashes quickly
N.B.: Max 3 W. If warning lights are in excess, the control panel processes will be endangered
with possible stop of all operations.
OPERATION AFTER A BLACK-OUT
When the power supply comes back the DL1 led turns on and remains on for all the time the gate
stays open. The led will turn off only once the gate is completely opened or closed.
It is recommended to fully open the gate. Let the gate close by itself or with automatic closing,
or wait until the blinker stops flashing before commanding it to close.
This will allow the gate to realign. If, motors were released and moved from the normal position
when closed during the blackout, the first movement after power returns must be complete.
If the black out occurs when the gate is still moving or when the gate is open and the first
command sent after the black out is a closing command, the closing of the gate will be carried
out with a total delay between the two gate leaves. Therefore, first the leaf M2 will close
completely; once it is off, M1 will start closing. This separate movement of the two gate leaves
is done to avoid their incorrect overlapping.
TECHNICAL SPECIFICATIONS
- Temperature range
- Humidity
- Power supply voltage
- Frequency
- Maximum absorption
- Power supply microinterruptions
- Maximum power SIGNAL output
- Maximum load of blinker output
- Current available for photocells and accessories
- Current available on radio connector
TECHNICAL RADIO SPECIFICATIONS (model B2-CRX)
- Reception frequency
433,92 MHz
- Impedence
52 ohm
- Sensitivity
>1 µV
- Feedback control
PLL
- Memory storage (codes)
1000
- All the inputs must be used as clean contacts because the power supply is generated
internally (safe voltage) in the card and it is set in a way to guarantee the use of the double
insulation and reinforced in relation to parts with hazardous voltage.
- Any external circuits connected to the outputs of the control board, must be carried out to
make sure the double or reinforced insulation is used in relation to parts with hazardous
voltage.
- All the inputs are run by a programmed integrated circuit which carries out a self-check at
the beginning of each operation.
-10 ÷ + 55°C
< 95% without condensation
230 o 120V~ ±10%
50/60 Hz
45 mA
100ms
24 Vdc 3W
40W with resistive charge
500mA 24 Vdc
200mA 24 Vdc
TROUBLE SHOOTING
After having carried out all connections, by carefully following the layout and having positioned
the gate in intermediate position, check the correct ignition of red LEDS DL6, DL7, DL8, DL9
and DL10.
In case of no ignition of the LEDS, always with gate in intermediate position, check the following
and replace any faulty components.
DL6
OFF
Stop button malfunction (if Stop is not connected, perform the jump
between COM A+ and STOP).
DL7 or DL8
OFF
Faulty photocells (In case the edge is not connected, carry out jumper
between COM A+ and PHOTO 1/PHOTO 2)
DL9 or DL10
OFF
Faulty safety edge (In case the edge is not connected, carry out jumper
between COM A+ and EDGE 1/EDGE 2)
During functioning with personnel present, with DIP 1 at ON, check that during opening of M1
and M2 the green DL2 and DL4 LEDS switch on and that during closing of M1 and M2 the red DL3
and DL5 LEDS switch on.
Or else, reverse the wires of the motor.
DL13 blue
ON
Some functions are enabled via smartphone, so via smartphone check
the card functions as the dips/trimmers status may not be true.
On the board there are resettable fuses which intervene in the event of a short circuit,
interrupting the output assigned to them.
In the event of troubleshooting, it is advisable to disconnect all the removable connectors and
insert them one at a time in order to more easily identify the cause of the fault.
37