9. Output relays
10. Working hours
44
is enabled by default, regardless of the protection device selected in
the TYPE OF APPLICATION section.
B) Monitoring of the electrical network
(Option available only for the two-pump device connected to a three-
phase electrical network).
Detection of correct phase sequence in the device power supply can
be enabled.
C) Phase consumption control
(Option available only for the two-pump device connected to a three-
phase electrical network).
This option (enabled by default) continuously controls the amperage
that circulates through each phase and, if it detects that one phase
consumes significantly more than the other two, it stops the operation
of the pump to prevent damage to the motor.
D) Supervision of the number of pump starts
If the function is enabled, the device will monitor the number of
consecutive starts of the pumps and, if it detects a high number of
continuous starts and stops, it will stop the pumps to avoid damaging
the installation as well as the pumps themselves.
E) Anti-blocking of pumps
The device will start the pumps for a few seconds if it detects that
the pump has been out of operation for a long period of time, in
order to prevent the pump from being blocked due to inactivity. The
days of pump inactivity can be individually adjusted for each pump to
lengthen/shorten the anti-blocking period of the pumps.
F) Pipe break detection
In systems that work with a pressure transducer, we can stop the
pump if it is detected that the pump is operating for a period of time
with a very low pressure, being unable to raise the pressure. This
effect can mean a break or large leak in the installation.
G) Locking the device
A 4-number PIN can be established, to be chosen by the installing
user, through which we will avoid changing important device
parameters for users without permission.
The device has 2 power-free relays, completely configurable by the user,
in order to report the status of the pumps or the device. In the general
device settings diagram that you can find in this same section you will
find the available options.
We can view the operating hours of pump 1 and pump 2 individually.