10.10 Optional: Connect the second sensor.
i ... adapter cable for sensors
k ... door contact
l ... yellow
m ... brown
10.11 Optional: Connect the third sensor.
i ... adapter cable for sensors
n ... flush trigger for disabled persons
o ... white
p ... green (for Y-sensor distributor 2/3, use "yellow" wire colour)
10.12 Connect the electronic module (K) to the second electrical T-distributor (c).
10.13 Place the electrical T-distributors into the cistern.
Install the cover plate
10.14 Insert the screws (s) into the tabs (r).
10.15 Turn the screws by 90°.
10.16 Fit the frame (t) and screw it down.
10.17 Connect the optical sensor to the electronic module.
10.18 Pull the protective foil off the cover plate.
10.19 Seal the cover plate, e.g. with Chromol (not part of the delivery scope,
see Accessories
10.20 Fit the cover plate (u) and screw it down.
11. Function
11.1 Leave the sensor area.
• The flush system will be activated.
• Flushing will stop automatically.
☞
An automatic hygiene flushing function after 24 hours of non-use has been factory-set.
Function with door contact (optional):
Pre-flushing takes place once when the door is closed.
There is a minimum time interval of 5 minutes between two pre-flushes.
If the door remains locked for more than one minute and the sensor or trigger for the
disabled is not activated during this time, the flush will be automatically activated
when the door is unlocked.
12. Adjusting the range
The range can be adjusted using an ECC2 function controller via the web appli-
cation.