Flint & Walling Commander Pro Manual De Instrucciones página 9

Idiomas disponibles

Idiomas disponibles

Menu Option
(4) Pass code enable
(5) Underload protection
Set Deadhead trip point:
Set Dry well trip point:
Set Dry well off time:
Set Underload trip point:
Set Underload off time:
(6) Bump mode
(Switch Control Mode)
Set bump mode
frequency:
Set bump mode duration: Sets the time duration of the ramp up
Set bump mode current:
(6) Standby Sensitivity
(Transducer Control Mode)
Set Standby frequency:
Set Standby Drawdown:
Set Standby current:
(7) Broken pipe mode
Set broken pipe run time:
Access menu options by pressing and holding edit and enter for 3 seconds .
Action
(Y/N) Sets 5 digit pass code using Up/
Down keys .
Default No .
(On, Off, Prime) Turns underload
protection on, off, or off for 30 minutes .
Default ON .
Default 1.5Hp Drive = 5.0 A
Default 2.0Hp Drive = 6.4 A
Default 3.0Hp Drive = 8.2 A
Default 5.0Hp Drive = 13.6 A
Default 1.5Hp Drive = 3.9 A
Default 2.0Hp Drive = 5.3 A
Default 3.0Hp Drive = 6.5 A
Default 5.0Hp Drive = 11.9 A
Auto, 15 to 240 Min, 12 Hrs, or 24 Hrs.
Default Auto.
Default 1 .5Hp Drive = 3 .9 A
Default 2 .0Hp Drive = 5 .3 A
Default 3 .0Hp Drive = 6 .5 A
Default 5 .0Hp Drive = 11 .9 A
Auto, 15 to 240 Min, 12 Hrs, or 24 Hrs .
Default Auto .
(On, Off) Leak detection.
Default On.
Sets bump mode threshold frequency.
Default 50 Hz.
for a bump in PSI (.5 to 2.0 sec.)
Default 0.5 sec.
Sets bump mode threshold detection
current.
Default 1.5Hp Drive = 3.3A
Default 2.0Hp Drive = 4.9 A
Default 3.0Hp Drive = 6.3 A
Default 5.0Hp Drive = 10.4 A
Parameters for allowing the drive go into
standby mode at no/low flow .
Sets Standby threshold frequency .
Default 50 Hz .
Sets the amount the system pressure
can fluctuate after low load is sensed
and still go into standby mode( .5 to 2 .0
PSI)
Default 0 .5 PSI
Sets Standby threshold detection
current .
Default 1 .5Hp Drive = 3 .3 A
Default 2 .0Hp Drive = 4 .9 A
Default 3 .0Hp Drive = 6 .3 A
Default 5 .0Hp Drive = 10 .4 A
(On/Off) .
Default ON .
(1/2 - 48) Hours
Default 24 Hours .
Flint & Walling © Copyright 2022. All rights reserved.
Pass code restricts parameters being changed by non-authorized
individuals . If pass code lost, Call 1-800-345-9422 for assistance .
Recommend that this is left On . Provides pump protection from
deadhead or dry well conditions . May need to be Off/Prime when
priming a centrifugal or if filling irrigation system .
If the motor current falls below this set point when drive has
ramped to maximum frequency, the drive will trip on Deadhead
Fault. Adjust down in increments of .2 if experiencing nuisance
deadhead trip.
If the motor current falls below this set point when drive has
ramped to maximum frequency, the drive will trip on Dry Well
Fault. Adjust down in increments of .2 if experiencing nuisance
dry well trip.
If set to "Off", dry well time is variable by Intelligent reset. This
can be set to fixed time off before restarting in a range of 15 to
240 minutes in increments of 15 minutes, or 12 or 24 hours if
desired.
If the motor current falls below this set point when drive has ramped
to maximum frequency, the drive will trip on Underload Fault . Adjust
down in increments of .2 if experiencing nuisance underload trip .
If set to "Off", underload time is variable by Intelligent reset . This
can be set to fixed time off before restarting in a range of 15 to 240
minutes in increments of 15 minutes, or 12 or 24 hours if desired .
Turns On or Off a small pressure boost if the drive detects a very
low load (leak condition). This will reduce the run time of the
pump and drive.
When the drive is running for 15 seconds below this frequency.
and current is below the BM current, the drive will ramp up for
the BM duration regardless of switch state to create a slight
overpressure.
By increasing this duration time, the amount of overpressure
for drawdown can be increased. Caution: Increasing this time
too much has the potential of creating a high over pressure
condition.
When the drive is running for 15 seconds below this current and
the frequency is below the BM frequency, the drive will ramp
up for the BM duration regardless of switch state to create an
overpressure drawdown.
When the drive is running for 15 seconds below this frequency . and
current is below the standby current, the drive will begin ramping the
motor speed down and monitor system pressure to go into standby
mode .
By increasing the drawdown psi setting, you can increase the amount
of pressure fluctuation allowed during the standby logic processing
and still allow the drive to go into standby mode .
When the drive is running for 15 seconds below this current and
frequency is below the standby frequency, the drive will begin
ramping the motor speed down and monitor system pressure to go
into standby mode .
Turn On/Off broken pipe trip . When On, if the drive is running the
pump continuously for the set time period, the drive will trip out on
"Broken Pipe" .
Define the time that the drive can run continuously before tripping on
Broke Pipe .
9