Menu Option
(8) Advanced features
Drive parameters
Motor Type
Manual run pump mode
Set manual pump
frequency:
Set manual pump run time: (1/2 - 48, Cont .) - Hours)
External control mode
Alarm In Relay
Drive status relay
Powered by Generator
Ramp up sensitivity
(Switch Control Mode)
Ramp down sensitivity
(Switch Control Mode)
Minimum Start-Up Time
(Switch Control Mode)
(9) Reset to factory defaults
(10) Control Settings
(Transducer Control Mode)
Transducer Calibration
Enter Pressure Gauge
Reading
PID Set Points
Set PID Control P 100-5000 Default: 400
Set PID Control D 1000-10000 Default: 5000
Set PID Control D 10-150 Default: 50
Pipe Fill Mode
Set Pipe Fill Time: 1-15 Minutes
Pipe Fill Mode (On, Off) Fill Pipe
Access menu options by pressing and holding edit and enter for 3 seconds .
Action
View the current output Hz, Amps & heat
sink temperature .
(Submersible/Above Ground) Change
setting for the type of pump motor
(Off/On) Sets pump to run without
pressure switch .
Default OFF
(50 - 80 Hz)
Default 60 Hz .
Default 24 Hours .
(Off/On) .
Default OFF .
(N/O/NC) Sets alarm in contact settings .
Default N/O .
(N/O/NC) Sets alarm out relay as
normally open or normally closed .
Default N/O .
(No/Yes)
Default No .
(1, 2, 3, 4, 5) Sets Ramp Up speeds.
Default 4.
(1, 2, 3, 4, 5) Sets Ramp Down speeds
Default 4.
0.5-5 Seconds
Default 1.3
Resets drive to factory defaults
Advance control settings for use with
Transducer .
Used to calibrate transducer reading with
external pressure gage .
20-80 PSI
Adjust Transducer feedback control
parameters .
Default 3 min .
Default: Off
Flint & Walling © Copyright 2022. All rights reserved.
Used for diagnostic purposes in troubleshooting overheating drive .
This option is used to change the setting for the type of pump and
motor the controller was set to use during the initial set-up menu .
Turn on a manual run condition at a set frequency for a defined
amount of time .
Set the constant frequency (motor speed) of the Pump . (only required
if manual mode ON)
Sets the time that the drive will run before shutting itself off . If set
for Cont . (typically not recommended), the drive will run continuously
until it is stopped manually . Broken pipe mode is not active when
manual run is on .
Determines if the Alarm In contacts trips out the drive or just puts it in
Standby Mode . If Off and the contacts wired to the Alarm In terminal
blocks are inverse of the Alarm in Relay settings, the drive trips out
on External Trip . (Used for protection like over pressure .) If On and
the contacts wired to the Alarm In terminal blocks close, the drive
goes to Standby Mode . (Used for control like a timer contact for an
irrigation system .)
If set to normally Open, drive will operate normally when the contacts
are open & trip (or go to standby mode) when contacts close .
(Example: An irrigation timer closes a contact to signal the drive to
run, the Alarm In Relay setting should be set to NC (Normal Closed)
for the drive to be active during the irrigation cycle .)
The state of the relay changes when the drive trips . Typically not for
use in most residential applications .
Set the drive circuitry to expect power delivered from a gas driven
generator . Depending upon application a 5-10% pressure drop of can
be experienced when the drive is running the pump & motor at full
speed .
If excessive pressure fluctuations on pressure gauge is noticed,
increase setting.
If excessive pressure fluctuations on pressure gauge is noticed,
increase setting.
The minimum time the drive will ramp up when coming out of
standby.
Resets the drive to the initial start-up menu for drive set-up .
Adjust value to match the pressure reading of the external pressure
gauge & press enter .
By increasing this duration time, the amount of overpressure for
drawdown can be increased . Caution: Increasing this time too much
has the potential of creating a high over pressure condition .
Adjustments can change the quickness of the drive reacting to
pressure changes to reduce excessive pressure fluctuations .
Sets the time limit that pipe fill mode is active .
Turns On/Off Fill Pipe mode . When Pipe Fill mode is on, the drive will
not trip out on Deadhead/Low PSI fault .
10