P R E - I N S TA L L AT I O N
Find a suitable mounting location:
•
Mount within wiring range of the LS0 luminaire. A total of 50 ft (15 m) of cable can be used,
from the X96 Ketra controller to the last LS0 luminaire, including cabling in between luminaire
segments.
•
The X96 Ketra controller, a Clear Connect Type X device, must be mounted within 75 ft (22.9 m) of its
assigned gateway. The X96 must have at least two Type X devices within 25 ft (7.5 m). Within a
subnet, groups or clusters of Type X devices must not be separated by greater than 25 ft (7.5 m). The
gateway and the Type X devices assigned to it must be on the same floor.
•
Mount a minimum of 3 ft (1.0 m) away from interference sources in the 2.4 GHz band, including
but not limited to microwaves, wireless access points, hotspots, baby monitors, thermostats,
and voice recognizing control devices.
•
Do not install the controller inside a third-party enclosure. Performance of Type X devices can
severely degrade if installed inside metal enclosures.
•
A minimum of 2 in (51 mm) of free space is required around each side of the controller (see
Figure 1), as well as above
the faceplate.
•
Mount the controller in a position where it can be easily
located and accessed if service or troubleshooting is
necessary.
•
Ensure that the reset button and output connector can be
accessed. See Figure 2.
•
Ensure there is sufficient space in front of the junction box to
drive the mounting screws and attach the top cover.
•
Ensure that the junction box is rotated to allow the output
wiring on the controller to route towards the first LS0
luminaire.