Password request. See parameters b10 and PAS.
Only displayed on screen.
Shown sequentially with the temperature: The controller is in demo mode, the con guration has not been made.
Calibration ongoing, therefore, avoid, as far as possible, opening the cold room during the process.
Flashing with temperature: Con guration has been changed from 1 to 2 evaporators or vice versa.
ADAPTIVE MODE ALERT MESSAGES (Only shown pressing the
key)
Defrost end error in 1/2 evaporator during the calibration, defrost has not ended due to temperature.
Error during calibration in 1/2 evaporator. There is not enough di erence in temperature between the cold room
probe and the evaporator probe.
It has not been possible to carry out the calibration due to a lack of stability in the system
(Excessive door opening, excessive oscillations in the lower pressure, etc.).
Error during normal operation (ADAPTIVE Mode active) in 1/2 evaporator. There is not enough di erence in
temperature between the cold room probe and the evaporator probe.
A lack of stability has been detected in the system (Excessive door opening, excessive oscillations in the low pressure,
etc.) during normal operation (ADAPTIVE Mode active).
The persistent lack of stability has led to the deactivation of the ADAPTIVE mode.
Excessive door openings have been detected during calibration and it has not been possible to calibrate.
Excessive door openings have been detected and the device cannot regulate in ADAPTIVE mode.
AN41504517847601-000102 | 5
© Danfoss | Climate Solutions | 2022.08