If the UPS system does not operate correctly, please solve the problem by using the table below.
Symptom
No indication and alarm in the front
display panel even though the mains
is normal.
The icon
and the warning
code flashing on LCD display and
alarm is sounding every second.
The icon
and
LCD display and alarm is sounding
every second.
The icon
and
on LCD display and alarm is
sounding twice every second.
Fault code is shown as 43 and the
icon
is lighting on LCD display
and alarm is continuously sounding.
Fault code is shown as 14 and the
icon
is lighting on LCD display
and alarm is continuously sounding.
Fault code is shown as 1, 2, 3, 4, 11,
12, 13, 14, 1A, 21, 24, 35, 36, 41, 42
or 43 on LCD display and alarm is
continuously sounding.
Battery backup time is shorter than
nominal value
The icon
and
LCD display and alarm is sounding
every second.
Segurança e harmonia
ININTERRUPTA
Possible cause
The AC input power is not connected
well.
EPO function is enabled.
flashing on
The external or internal battery is
incorrectly connected.
UPS is overload
UPS is overloaded. Devices connected
to the UPS are fed directly by the
electrical network via the Bypass.
is flashing
After repetitive overloads, the UPS is
locked in the Bypass mode. Connected
devices are fed directly by the mains.
The UPS shut down automatically
because of overload at the UPS output.
The UPS shut down automatically
because short circuit occurs on the
UPS output.
A UPS internal fault has occurred.
There are two possible results:
1. The load is still supplied, but directly
from AC power via bypass.
2. The load is no longer supplied by
power.
Batteries are not fully charged
Batteries defect
flashing on
Fan is locked or not working; or the
UPS temperature is too high.

4. Troubleshooting

Remedy
Check if input cable firmly connected
to the mains.
Set the circuit in closed position to
disable EPO function.
Check if all batteries are connected
well.
Remove excess loads from UPS
output.
Remove excess loads from UPS
output.
Remove excess loads from UPS
output first. Then shut down the UPS
and restart it.
Remove excess loads from UPS
output and restart it.
Check output wiring and if connected
devices are in short circuit status.
Contact your dealer
Charge the batteries for at least 7
hours and then check capacity. If the
problem still persists, consult your
dealer.
Contact your dealer to replace the
battery.
Check fans and notify dealer.
PH 9360 | PH 9301
Uninterruptable Power Supply
EN
63