11. Operation in Fault mode
1) When Fault LED illuminates and the buzzer beeps continuously, it means that there is a fatal error in the UPS. Users
can get the fault code from display panel. Please check the trouble shooting table in chapter 4 for details.
2) Please check the loads, wiring, ventilation, utility, battery and so on after the fault occurs. Don‟t try to turn on the UPS
again before solving the problems. If the problems can‟t be fixed, please contact the distributor or service people
immediately.
3) For emergency case, please cut off the connection from utility, external battery, and output immediately to avoid more
risk or danger.
12. Operation of changing battery numbers
1) This operation is only available for professional or qualified technicians.
2) Turn off the UPS. If the load couldn‟t be cut off, you should remove the cover of maintenance bypass switch on the
rear panel and turn the maintenance switch to "BPS" position first.
3) Switch off the input breaker, and switch off the battery breaker (only available for long-run model).
4) Remove the cabinet, and then modify the jumper on the control board to set the battery numbers (refer to NOTE
below). Then disconnect battery wire for standard model and modify the battery pack carefully. After complete the
changes, put the cabinet back.
NOTE: JP1 setting on the control board: please shorts the Pin5 & Pin6 and Pin7 & Pin8 for 20 pcs batteries; shorts the
Pin5 & Pin6 or Pin7 & Pin8 for 19 pcs batteries; and keeps every pin open for 18 pcs batteries.
5) Switch on the input breaker and the UPS will enter Bypass mode. If the UPS is in maintenance Bypass mode, turn the
maintenance switch to "UPS" position and then turn on the UPS.

3.6. LCD Setting

Parameter 1
Parameter 2 Parameter 3
Code
01
Output voltage
02
Output Frequency
03
Voltage range for bypass
04
Frequency range for bypass
05
ECO mode enable/disable
06
Voltage range for ECO mode
07
ECO mode frequency range setting
08
Bypass mode setting
09
Battery backup time setting
10
Programmable output setting**
11
Shutdown point for programmable output
12
Hot standby function enable/disable
13
Battery voltage adjustment
14
Charger voltage adjustment
15
Output voltage adjustment
*Y means that this program can be set in this mode. | **Programmable output setting is not supported by Rack models.
Segurança e harmonia
ININTERRUPTA
There are three parameters to set up the UPS.
Parameter 1: It's for program alternatives.
There are 15 programs to set up. Refer to the table.
Parameter 2 and parameter 3 are the setting options or values for each
program.
Description
Bypass
AC
ECO
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Uninterruptable Power Supply
3. Operations
Battery
CVCF
Battery
test
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
PH 9360 | PH 9301