Specification
lt's recommended to thoroughly read technical data stated in this page prior to adjusting the Internal Setting to your application needs.
1) Voltage: 230VAC
2) Display: LCD digital display
3) Output: Voltage-free or voltage output, Rating 16A/230 V
4) Circuitry consumption: 8 VA
5) Temperature indication: C or °F selectable to users
6) Temperature control range: Room: 5~35°C (40~95°F) Floor: 5~45°C (40~113°F)
7) Temperature display range: -10~50°C (14~122°F), accuracy ±0.1 °C (0.2°F)
*no decimal indicator above 100°F
8) Comfort set point
adjustment range:
Room mode: Range 5~35°C (40~95°F) default Cool 24°C (75°F), Heat 21°C (70°F)
Floor mode & Room+Floor-Limitation mode: Range 5~45°C (40~113°F) default Floor-mode 26°C (78°F)
Room+Floor-Limitation mode: 21°C (70°F) (Room Temp. Performs the priority commands)
9) Economy set point
adjustment range:
Room mode: Range 5~35°C (40~95°F) default Cool 27°C (80°F), Heat 16°C (60°F) Floor mode & Room+Floor-Limitation mode:
Range 5~45°C (40~113°F) default Floor-mode 21°C (70°F)
Room+Floor-Limitation mode: 16°C (60°F) (Room temp. Performs the priority commands)
10) Floor temperature limitation adjustment range:
For Floor mode & Room+Floor-limitation only:
High Limit.: 20~45°C (68~113°F) default 29°C (85°F)
Lo Limit.: 5 ~20°C (40-68°F) default 15°C (59°F)
* In floor-mode, Lo Limit. Performs as low-temperature protection, Hi-Limit. Functions as floor-temp. Limitation.
*ln Room + Floor Limitation mode, only Hi-Limit.
11) Temperature sensor : NTC 10K Ohm at 25°C
12) Switching differential (Hysteresis) selectable to users
Room & Room+Floor-Limit. mode: 0.2/0.4/0.6/0.8/1°C ~ 0.4/0.8/1.2/1.6/2°F default 0.4°C/0.8°F
Floor mode only: 0.6/1/2/3°C ~ 1.2/2/4/6°F default 1°C/2.0
13) Floor-limitation switching differential: 2.0°C (4.0°F) prefixed, not adjustable.
In Room+Floor Limit mode, after floor temperature reached floor-limit. Setpoint, heating system ON/OFF shall perform as
graphic descriptions below, before users change the setpoint.
14) Frost protection: Prefixed, not adjustable to users. Effects when thermostat is OFF by Stand-by(
) mode. Room mode&
Room+floor limit. mode 5°C (40°F). Floor mode 10°C (50°F)
15) Shortest cycle ratę protection: 3 minutes, effects onlyin Cool-mode.
16) Materiał: Non flammable plastics ,standard white or RAL9010
17) Storage temperature:-10 ~60°C.
18) Dimension: 87.0 H x 87.0 W x 51.5 D mm
For choosing the required floor-limitation setpoint; it's recommended tocarefully check the material used in constructing your
floor before selection. lt's advised to consult with your builder.
Contact your distributor or technician for advice in order to obtain the ideal temperature for the coziest possible home.
All factory default settings can be found in the page "SPECIFICATION", it's advised to look through them before changing the
internal settings.