LED
26 mm
(Hidden)
76 mm
8.4 mm
NRX-USB interface status LED
Status
LED State
Green pulse Device OK and connected
Power-on initialisation
Amber ON
Fault
Amber blink Device has an internal trouble
Serial (USB)
Green blink
communication
RF communication
Blue blink
NRX-USB(-PRO)
RADIO SYSTEM USB INTERFACE
INSTALLATION AND USER INSTRUCTIONS
96 mm
USB Connector
- Type A
13 mm
50°C
0°C
Meaning
Device OK but not recognized
Interface is receiving data from
the PC application
Interface is receiving data from
an RF device
Notifier by Honeywell, Brooks Road, Lewes, East Sussex, BN7 2BY, UK
DESCRIPTION
The NRX-USB(-PRO) is an interface that connects to a PC
through a USB port and allows communication with Notifier NRX
RF devices. The NRX-USB(-PRO) is powered directly by the USB
31 mm
port.
This radio device complies with the requirements of 2014/53/EU
for conformance with the RED directive.
SPECIFICATIONS
Supply Voltage:
Supply Current:
USB standard:
USB connector:
Radio Frequency:
RF Output Power:
Range:
Relative Humidity:
INSTALLATION
The NRX-USB(-PRO) has an adjustable USB connector in order to
maximize the RF coupling with radio communicating devices, and
to change its profile when connected to a portable PC.
Do not connect the NRX-USB(-PRO) interface until the correct
drivers have been installed on the target PC.
Download the latest version of the AgileIQ
(with the correct interface drivers) from a trusted source - see the
Radio Programming and Commissioning Manual for the installation
procedure.
Only plug the RF interface into a spare USB port on the PC
when requested.
Note that when the interface is attached, Windows may take a
number of seconds to recognize the new hardware correctly;
always wait a short period for the LED to change from yellow
to green before proceeding with any other operation.
LED INDICATORS
The interface is equipped with an RGB LED, giving an indication of
power and communication (both RF and USB) status (see table).
PROGRAMMING
Used in conjunction with the AgileIQ
the RF interface is used to program and communicate with Notifier
NRX RF fire detection devices. For information on setting-up,
commissioning and monitoring an RF mesh network, see the
Radio Programming and Commissioning Manual - ref. N200-
306-00.)
NOTE: Do not run more than one interface at a time to
commission devices or carry out a site survey in an area.
Hereby,
equipment type
The full text of the EU DoC can be requested from:
4.3 – 5.5V Direct Current (DC)
33mA typical @ 5VDC
USB 2.0 (full speed)
Type A
865-870 MHz;
13 dBm (@ 5VDC)
130m (typ. in free air)
10% to 93% (non-condensing)
radio interface software
®
Device Interface Software,
®
Patents Pending
EU Declaration of Conformity
Notifier by Honeywell declares
that the radio
NRX-USB(-PRO)
is in compliance
directive 2014/53/EU
E N G L I S H
I 56- 4211- 003
with
I56-4211-003
loading

Resumen de contenidos para Honeywell NOTIFIER NRX-USB-PRO

  • Página 1 Notifier by Honeywell declares that the radio equipment type NRX-USB(-PRO) is in compliance with directive 2014/53/EU The full text of the EU DoC can be requested from: [email protected] I56-4211-003 Notifier by Honeywell, Brooks Road, Lewes, East Sussex, BN7 2BY, UK...
  • Página 2 NOTA: Non eseguire in contemporanea più di una procedura di configurazione o di analisi del sito alla volta. Dichiarazione di Conformità UE Il fabbricante, Notifier by Honeywell dichiara che il tipo di apparecchiatura radio NRX-USB(-PRO) è conforme alle Direttiva 2014/53/EU.
  • Página 3 NRX-USB(-PRO) conforme con la Directiva 2014/53/EU. El texto completo de la declaración UE de conformidad está disponible. Puede solicitar el documento a: [email protected] I56-4211-003 Honeywell Life Safety Iberia, S.L. C/ Pau Vila, 15-19, 08911 Badalona (Barcelona) Espana...
  • Página 4 ANMERKUNG: Nicht mehr als eine Schnittstelle gleichzeitig verwenden, um die Geräte im Umfeld zu installieren. Vereinfachte EU-Konformitätserklärung Hiermit erklärt Notifier by Honeywell, dass der Funkanlagentyp NRX-USB(-PRO) der Richtlinie 2014/53/EU entspricht. Der vollständige Text der EU-Konformitätserklärung ist unter der folgenden verfügbar: [email protected]...
  • Página 5 Notifier by Honeywell déclare que l’équipement radioélectrique du type NRX-USB(-PRO) est conforme à la directive 2014/53/EU. Le texte complet de la déclaration UE de conformité est disponible à: [email protected] I56-4211-003 Honeywell Life Safety SA, Liege Airport Business Park B50, 4460 Grâce-Hollogne - België...