HAEGER Digi Desumi 16 DE-D16.013A Instrucciones De Uso página 8

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 45
4. Checking for presence of refrigerant
The area shall be checked with an appropriate refrigerant detector prior to and
during work, to ensure the technician is aware of potentially flammable
atmospheres. Ensure that the leak detection equipment being used is suitable
for use with flammable refrigerants, i.e., no sparking, adequately sealed or
intrinsically safe.
5. Presence of fire extinguisher
If any hot work is to be conducted on the refrigeration equipment or any
associated parts, appropriate fire extinguishing equipment shall be available to
hand. Have a dry powder orCO2 fire extinguisher adjacent to the charging area.
6. No ignition sources
No person carrying out work in relation to a refrigeration system which
involves exposing any pipe work that contains or has contained flammable
refrigerant shall use any sources of ignition in such a manner that it may lead
to the risk of fire or explosion. All possible ignition sources, including cigarette
smoking, should be kept sufficiently far away from the site of installation,
repairing, removing and disposal, during which flammable refrigerant can
possibly be released to the surrounding space. Prior to work taking place, the
area around the equipment is to be surveyed to make sure that there are no
flammable hazards or ignition risks. "No Smoking" signs shall be displayed.
7. Ventilated area
Ensure that the area is in the open or that it is adequately ventilated before
breaking into the system or conducting any hot work. A degree of ventilation
shall continue during the period that the work is carried out.
The ventilation should safely disperse any released refrigerant and preferably
expel it externally into the atmosphere.
8. Checks to the refrigeration equipment
Where electrical components are being changed, they shall be fit for the
purpose and to the correct specification. At all times the manufacturer's
maintenance and service guidelines shall be followed. If in doubt consult the
manufacturer's technical department for assistance.
The following checks shall be applied to installations using flammable
refrigerants:
The charge size is in accordance with the room size within which the
refrigerant containing parts are installed;
The ventilation machinery and outlets are operating adequately and are
not obstructed;
6
loading