06: Bypass enable/disable when UPS is off 
Interface 
07: Bypass voltage range setting 
Interface 
08: Programmable outlets enable/disable 
Interface 
09: Programmable outlets setting 
Interface 
00: Exit setting 
 
www.powerwalker.com 
parameter 3 is from +3V to +12V of the nominal voltage.   
LLS: Low loss voltage in ECO mode in parameter 2. 
For 208/220/230/240 VAC models, the setting range in 
parameter 3 is from ‐7V to ‐24V of the nominal voltage.   
For 110/115/120/127 VAC models, the setting voltage in 
parameter 3 is from ‐3V to ‐12V of the nominal voltage.   
Setting 
Parameter 3: Enable or disable Bypass function. You may 
choose the following two options:   
ENA: Bypass enable 
DIS: Bypass disable 
 
Setting 
Parameter 2 & 3: Set the acceptable high voltage point and 
acceptable low voltage point for Bypass mode by pressing the 
Down key or Up key. 
HLS: Bypass high voltage point 
For 208/220/230/240 VAC models: 
230‐264: setting the high voltage point in parameter 3 from 
230Vac to 264Vac.   
For 110/115/120/127 VAC models:   
120‐132: setting the high voltage point in parameter 3 from 
120Vac to 132Vac 
LLS: Bypass low voltage point 
 
For 208/220/230/240 VAC models: 
170‐220: setting the low voltage point in parameter 3 from 
170Vac to 220Vac 
For 110/115/120/127 VAC models:   
85‐115: setting the low voltage point in parameter 3 from 
85Vac to 115Vac. 
Setting 
Parameter 3: Enable or disable programmable outlets.   
ENA: Programmable outlets enable 
DIS: Programmable outlets disable 
 
Setting 
Parameter 3: Set up backup time limits for programmable 
outlets.   
0‐999: setting the backup time limits in minutes from 0‐999 for 
programmable outlets which connect to non‐critical devices on 
battery mode. 
 
Page 12
EN