Coelbo PANELMATIC easy M Manual De Instrucciones página 35

Idiomas disponibles

Idiomas disponibles

9. STARTUP
Before starting this device, read the previous sections,
especially "Operating modes" and "Electrical connec-
tions".
Follow this basic commissioning steps:
1. Turn on the power supply using the integrated
MCB.
2. Set the rated current of each pump:
- Hold A for 3 seconds.
- Screen will display the current value of intensity
blinkng and A led-light will shine.
- By mean of
and
current indicated on the nameplate of the pump.
See Note 1.
- Confirm with
(P6).
3. Configuration of the installation voltage (optional).
PANELMATIC is constantly reading the installation
voltage but, it is necessary to set the desired value, in
order to activate low-voltage and over-voltage alarms.
- Hold V for 3 seconds.
- Choose the value between the range [OFF, 110,
220, 230, 380, 400]V.
- Confirm with
(P6).
4. Choose the operation MODE inside the BASIC
PROGRAMMATION MENU (10). The unit is ready to be
programmed. There are multiple adjustment options
to be made through the basic and advanced pro-
gramming menus. See the next chapter.
5. Finally, press the START/STOP push-button in
order to start the unit.
Note 1: it is important to introduce exactly the
rated current specified on the pump nameplate.
If a new pump is installed, this process should be
repeated.
Note 2: for 2 pumps models:
- A value in Amps will be set in both pumps.
- V and all the other parameters will be set in
the master unit.
10. BASIC PROGRAMMATION MENU
- Hold
for 3 seconds.
- By mean of
or
- Confirm with
and go to next step.
- Save and quit the MENU, at any time, with
- This is the parameters sequence (in bold default
values):
TYPE
Operation mode (see 5.2):
- MF1: probe mode or simultaneous stop mode.
- MF2: flow switch mode or sequential stop
mode.
MF1 MF5
- MF3: pressure transmitter mode.
- MF4: filling mode with flow switches
- MF5: filling mode with probes.
- MF6: timed mode (only in stand-alone opera-
tion)
(*) When choosing P02 (2 pumps) the operation mode
must be set only in the MASTER unit.
will be adjusted the rated
values can be changed.
DESCRIPTION
When choosing MF3 (pressure transmitter mode):
Non available on Easy models
It.
TYPE
1
16.0
3
(14.5)
(230)
0.5
4
15.5 Start pressure (bar/psi).
(7)
5
d0.5
d1.0
6
ct0
ct9
7
dt0
dt9
8
PSI
bar
9
t10
t16
10
P0.0
P16
11
t01
t99
12
rs0
rs1
In case of having selected MF6 -timed mode- (ver 5.2.6):
It.
TYPE
3
tAu
t00
.
4
rs0
These operation mode applies only for single pump.
9
DESCRIPTION
Stop pressure (bar/psi).
In case of 2-pumps set
operation, it must be
set a gap between start
pressures (Pstart1-Pstart2)
or stop pressures (Pstop1-
Pstop2).
Sets a time delay between
0 and 9 seconds to the
start.
Sets a time delay between
0 and 9 seconds to the
stop.
Can be selected the pres-
sure units displayed, bar
or psi.
Can be choosen the pres-
sur transmitter range, 0-10
bar or 0-16 bar.
With P_xx is activated a
minimum operating pres-
sure. Under this pressure
it trips alarm (A11).
Time, in seconds, under
minimal pressure neces-
sary to activate A11.
rs0: end.
rs1: Restore factory set-
tings (rs1).
DESCRIPTION
tAu: auto learning.
The pump will start at the end
of the configuration process and
after pressing START/STOP.
In the first operation cycle it will
stop by reading the absorbed
current. It will save the elapsed
time in memory. From this mo-
ment, this time will be applied,
t99
decreased by 10%, for the auto-
matic stop of the pump.
txx: time in minutes that the
pump will keep running.
t00: pump will stop when detec-
ting low current consumption
but it will not trip A01 ALARM.
rs0: Exit saving data.
rs1
rs1: Restore factory settings (rs1).
3.0
(43)
1.0
(14.5)
d0.5
ct0
dt0
bar
t10
P0.0
t20
rs1
loading