8. CONTROL PANEL
S
P5
P6
P7/P8
- QR Code is a direct access to the instructions ma-
nual.
- LED indicator lights:
Following table summarizes the meaning of the LED
lights, where:
• O means LED light lit.
• ( ( O ) ) means blinking LED.
REF.
LEDS
STATE
L1
Amp
O
L2
Volt
O
L3
bar/psi
O
O
L4
alarm
( ( O ) )
O
start
L5
stop
( ( O ) )
QR
Amp
Volt
bar/psi
START
STOP
V
P1
P2
P3
P4
MEANING
On the screen is displayed the
instantaneous current consump-
tion in Amps or, when the screen is
flashing, the user is configuring the
nominal current of the pump.
On the screen is displayed the
instantaneous voltage in Volts or,
if the screen is flashing, the user is
configuring the nominal voltage to
be able to detect undervoltage and
overvoltage alarms.
Is displayed on screen instanta-
neous pressure in bar or psi. Mode
3.
Final alarm. Need of manual inter-
vention to be restored.
Active alarm with automatic restore
system in process.
Pump operating manual mode.
Pump operating auto mode.
- Display (S) with 3 digits that can show:
• State:
• OFF: inactive.
• ON: active and with nominal current already
L1 L1
configured.
• ON + blinking segment: pump on.
L2
• XX.X: instantaneous pressure (bar or psi) only in
L3
operation mode 3.
• Instantaneous current drawn by the pump in Amps
L4
after short press on button A (P1).
• Instantaneous voltage after short press on button
V (P2).
L5
• Configuration parameters of the PROGRAM-
MATION MENU.
• Alarm code.
- Push-buttons:
The following table summarizes the meaning and ope-
ration of the push-buttons.
REF. SYMB.
PULSA-
P1
A
P2
V
P3
P
P4
P5
P6
P7
P8
8
ACTION
TION
On the screen is displayed the ins-
tantaneous current consumed. If we
click!
are already watching it, we return
to pressure visualization.
Configuration of the rated current
3"
of the pump.
On the screen is displayed the
click!
voltage supplied.
Configuration of the installation
voltage, to be able to detect low
voltage and overvoltage alarms.
3"
Using the arrows will be selected
between the range of values. [OFF,
110, 220, 230, 380, 400]V.
Confirm with .
To switch pressure units from bar
to PSI and vice versa. Hold for 3
3"
seconds, select with the arrows and
confirm with .
It switches from state ON to OFF
click!
and viceversa.
Manual start: it will start the pump
and it will keep running until the end
of the pulsation.
3"
WARNING: in this condition are not
considered external activations of
start/stop.
To enter the PROGRAMMING
3"
MENU.
Once inside the PROGRAMMING
MENU it allows to save and quit
click!
at any level of the configuration
sequence.
To confirm the value of the different
click!
programming parameters as well as
restore alarms on the screen.
To increase and decrease the value
click!
of the different parameters.