3.12 Diagrama de conexión en paralelo de fase partida (120/240Vac)
(Region:US)
Inverter
① DC
Breaker
①②③ DC Breaker for battery
SUN 5K-SG-EU: 150A DC breaker
SUN 6K-SG-EU: 200A DC breaker
SUN 7.6K-SG-EU: 200A DC breaker
SUN 8K-SG-EU: 250A DC breaker
⑤⑦⑨ AC Breaker for grid port
SUN 5K-SG-EU: 40A AC breaker
SUN 6K-SG-EU: 40A AC breaker
SUN 7.6K-SG-EU: 40A AC breaker
SUN 8K-SG-EU: 63A AC breaker
④⑥⑧ AC Breaker for
backup load port
SUN 5K-SG-EU: 40A AC breaker
SUN 6K-SG-EU: 40A AC breaker
SUN 7.6K-SG-EU: 63A AC breaker
SUN 8K-SG-EU: 63A AC breaker
⑩ AC Breaker
Depends on Home Load
Battery pack
The primary side of the CT
needs to be clamped on the
Grid live line.
Master inverter
Advanced Function
Parallel
Modbus SN
A Phase
B Phase
01
Master
C Phase
Slave
CAN
L wire
Inverter
No.3
(slave)
Inverter
No.2
(slave)
② DC
Breaker
Inverter
No.1
(master)
③ DC
Breaker
CT
Arrow pointing
to
inverter
Slave Inverter
Advanced Function
Parallel
Modbus SN
A Phase
B Phase
02
Master
Paral.
Set3
C Phase
Slave
N wire
N L2 L1 N L2 L1 N L2 L1
Grid
N L2 L1 N L2 L1 N L2 L1
Grid
N L2 L1 N L2 L1 N L2 L1
Grid
CT2
Grid
PE
N
L2 L1
Slave Inverter
Advanced Function
Parallel
Modbus SN
03
Master
Paral.
Set3
Slave
- 24-
PE wire
GEN
Load
⑤
GEN
Load
⑥
⑦
GEN
Load
⑧
⑨
CT1
⑩ AC
Breaker
Home Load
Backup Load
A Phase
B Phase
Paral.
Set3
C Phase
Parallel A Parallel B
Ground
④
L1
L2
N
PE