toscano Vigilec ZERO V1Z Manual De Usuario página 48

Ocultar thumbs Ver también para Vigilec ZERO V1Z:
Idiomas disponibles

Idiomas disponibles

14. TECHNICAL SPECIFICATIONS
V1Z
Power supply
Motor current range
Protections
Level control
Inhibition time (flow switch)
Underload setting (Imax)
Overload setting (Imin)
Restart time
Control voltage (level probe/
float switch)
External control (EXT. ON/OFF)
Max. terminal cross section
Cable glands
Low level output
Recording information
(PUMPCHECK)
Size*/Weight/IP/Temperature
V1Z-F
Power supply
Motor current range
Protections
Level control
Inhibition time (flow switch)
Underload setting (Imax)
Overload setting (Imin)
Restart time
Control voltage (level probe/
float switch)
External control (EXT. ON/OFF)
Max. terminal cross section
Cable glands
Low level output
Recording information
(PUMPCHECK)
Size*/Weight/IP/Temperature
*HEIGHTxWIDTHxDEPTH
44
230 V AC or 400 VAC (depending on model) / -20%...+30% /
50/60Hz
1...18 A / AC3
Underload, overload, phase failure and over-voltage
Two probes, timed probe, no probes or flow switch
Selectable in 15, 30, 60, or 90 seconds
OFF - 0,5... 21 A (jump in 4 seconds)
0,5...21 A (jump in 7 seconds)
Disabled (OFF) or adjustable from 3 minutes up to 8 hours
12 V AC
Dry contact or voltage from 6 to 24 V AC/DC
10 mm² (power) / 4 mm² (control)
Supply and Pump: 2xM20 / Control: 2xM16
Voltage free (up to 5A-250 V max)
Module identification number, pump running hours, pump
starts, pump alarms and last alarm trip current
240 x 190 x 110 mm (H x W x D) / 1,82 kg / IP65 / -10...+55 ºC
230 V AC or 400 V AC (depending on model) / -20%...+30% /
50/60Hz
10...25 A / AC3
Underload, overload, phase failure and over-voltage
Two probes, timed probe, no probes or flow switch
Selectable in 15, 30, 45, 60, 75 or 90 seconds
OFF - 10... 30 A (jump in 4 seconds)
10...30 A (jump in 7 seconds)
Disabled (OFF) or adjustable from 3 minutes up to 8 hours
12 V AC
Dry contact or voltage from 6 to 24 V AC/DC
10 mm² (power) / 4 mm² (control)
Supply and Pump: 2xM25 / Control: 2xM16
Voltage free (up to 5A-250 V max)
Module identification number, pump running hours, pump
starts, pump alarms and last alarm trip current
240 x 190 x 110 mm (H x W x D) / 1,85 kg / IP65 / -10...+55 ºC
loading

Este manual también es adecuado para:

Vigilec zero v1z-f