Set the minimum current 0.2A above the pump consumption.
5A + 0,2A = 5,2A
5. 0
5. 2
For three-phase pumps, do not set the parameter below 0.5 A.
Restart time
In case of operating with only 1 probe, without probes or with a fl ow switch, the restart
time must be set correctly after a lack of water.
The reset time is a confi gurable time that starts when it detects a lack of water until the
well is refi lled. This time will be calculated according to the case.
It can be switched OFF or set from 3 minutes to 8 hours.
Adjust according to the recovery time of your well, f.e. 45 minutes.
45
41