Installation Instructions
Step 1
Confirming RF-3000LE is Calibrated
Start up your Rionfuser™ RF-3000LE and it will perform a Self Test. If the Cal Due date has passed or is within the life of your
project, then STOP, and contact your Orion Representative for instructions on how to get your machine recalibrated.
Watts disclaims all liability for installations performed with a Rionfuser past its calibration date.
For additional information reference the RF-3000LE Instruction Manual included in the carrying case.
Step 2
Preparing the Pipe
Material preparation is essential to achieving satisfactory fusion results. Deburr all field-cut pipe ends. Following the coupling
insertion depth chart, mark the coupling insertion depth from the end of the pipe/fitting to insure that the coupling is properly
positioned during the fusion cycle. Then, using 60 grit emery cloth, abrade the marked ends of the pipe and fitting to remove
the natural "sheen" of the plastic. After abrading, clean all joint surfaces thoroughly with isopropyl alcohol to remove any dirt,
grease and the contaminants left from the sandpaper and any other foreign matter from the surface. We suggest using a spray
bottle with 90% or higher isopropyl alcohol to soak a lint resistant cloth to thoroughly wipe the joint surface clean.
Coupling Insertion Depth Marking
Pipe Diameter
Mark Distance from Pipe End
in.
1 1/2
2
3
4
6
8
10
12
Mark coupling depth
Step 3
Joint Assembly
Insert the prepared ends of the pipe/fitting into both hubs of the Rionfuse CF coupling. Double check the markings to verify
proper seating of the pipe.
Insert into coupling and verify
proper seating
in.
1
1
1 3/8
1 3/8
2
2 5/8
2 5/8
2 5/8
Abrade surface
4