DP/PA coupler Ex [ia], 6ES7157-0AD82-0XA0; as of product state 2
Product Information Leaflet
This product information leaflet contains important information about the DP/PA coupler.
Further information
Further information about the module is provided in the
• manual DP/PA Link and Y Link Bus Couplings (A5E00193841)
• manual Automation Systems Principles of Intrinsically-Safe Design (A5E00206201).
• Informations regarding FM Approval and corresponding notes for commissioning is contained in
FM-Approval Intrinsic Safety Control Drawing (A5E00237843).
• Internet:
http://www.siemens.com/automation/service&support
Approval
You will find the current approvals on the type plate of the respective product.
Manufacturing site
Siemens AG, DI FA MF-EWA, Werner-von-Siemens-Str. 50, D-92224 Amberg
Certification
FISCO POWER SUPPLY
II 3 G (1) G Ex ec [ia Ga] IIC T4 Gc
II 3 G (1) D Ex ec [ia IIIC Da] IIC T4 Gc CE
Note
The DP/PA coupler with
FISCO POWER SUPPLY
II 3 G (1) G Ex ec [ia Ga] IIC T4 Gc
II 3 G (1) D Ex ec [ia IIIC Da] IIC T4 Gc
certification can be used as a PROFIBUS device of device category 3G inside zone 2 hazardous
areas. Intrinsically safe electrical apparatus of device categories 1G, 2G and 3G for zones 0, 1
and 2; as well as of device categories 1D, 2D and 3D for zone 20, 21, and 22 may be connected.
Maintenance
The module is maintenance-free. In the event of need for repair, the module must be sent to the place of
manufacture. No repairs may be carried out anywhere else.
Installation
• The equipment shall only be used in an area of no more than pollution degree 2, as defined in IEC
60664-1.The equipment shall be installed in a suitable enclosure that provides a degree of protection
not less than IP54 in accordance with IEC 60079-7.
• If a temperature of > 70 °C is reached in the cable or at the cable entry of this housing under
operating conditions, or if a temperature of > 80 °C can be reached at the junction of the conductors
under operating conditions, the temperature-related properties of the cables must correspond to the