3.6 Float switch leak detection input
3
4
Sensor excitation voltage: 5VDC
Float switch type: NC
3.7 PTC leak detection input
4
5
Sensor excitation voltage: 24VDC
Max current: 120mA
Warning: PTC and Float Switch leak sensor cannot be connected in the same time.
3.8 Ext power input
6
Max voltage applied: 24VDC
Power min: 10W
Warning: Mains power (connector J6) MUST be disconnected when device powered by 24VDC.
3.9 Flowmeter input
7
8
Voltage excitation: 3.3VDC
Input type: pull up with internal resistor
Volt free contacts (Open Collector or Reed Switch) compatible
Max frequency: 300Hz
3.10 4..20mA input
9
10
Voltage excitation: 24VDC
Input type: 4..20mA current loop
Current limited internally to 25mA
Flo
J3
Float switch
Float switch
J3
PTC
PTC
J3
+24VDC input
J2
+
-