Siemens GIB 1 Serie Instrucciones De Montaje página 9

Actuador de acción rotativa
Ocultar thumbs Ver también para GIB 1 Serie:
Voltage
AC 24 V
AC 230 V
Mixed
de
Anschluss
Kabelbezeich-
nungen
Antriebe
AC 24 V
Antriebe
AC 230 V
Hilfsschalter
Rückführ-
potentimeter
en
Connection
Wire
designations
AC 24 V
actuators
AC 230 V
Actuators
Auxiliary switch
Feedback
potentiometer
Smart Infrastructure
Switch A (S1)
辅助开关 A
스위치 A
スイッチ A
AC 24 V
L1 (phase)
L2
L3
L
(phase)
X
AC 24 V
AC 230 V
Kabel
Code
Nr.
Farbe
G
1
rot
G0
2
schwarz
Y1
6
violett
Y2
7
orange
Y
8
grau
U
9
rosa
N
4
blau
Y1
6
schwarz
Y2
7
weiss
Q11
S1
grau/rot
Q12
S2
grau/blau
Q14
S3
grau/rosa
Q21
S4
schwarz/rot
Q22
S5
schwarz/blau
Q24
S6
schwarz/rosa
a
P1
weiss/rot
b
P2
weiss/blau
c
P3
weiss/rosa
Cable
Code
No.
Color
G
1
red
G0
2
black
Y1
6
purple
Y2
7
orange
Y
8
gray
U
9
pink
N
4
blue
Y1
6
black
Y2
7
white
Q11
S1
gray/red
Q12
S2
gray/blue
Q14
S3
gray/pink
Q21
S4
black/red
Q22
S5
black/blue
Q24
S6
black/pink
a
P1
white/red
b
P2
white/blue
c
P3
white/pink
431926850-AL
Switch B (S4)
辅助开关 B
스위치 B
スイッチ B
AC 24 V
L1 (phase)
L2
L3
 L
(phase)
X
AC 230 V
AC 24 V
Bedeutung
Abkürzung
RD
System Potential AC 24 V
BK
Systemnull
VT
Stellsignal AC 0 V "Uhrzeigersinn"
OG
Stellsignal AC 0 V "Gegenuhrzeigersinn"
GY
Stellsignal DC 0...10 V, 0...35 V
PK
Stellungsanzeige DC 0...10 V
BU
Nullleiter
BK
Stellsignal AC 230 V, Uhrzeigersinn
WH
Stellsignal AC 230 V,Gegenuhrzeigersinn
GYRD
Schalter A Eingang
GYBU
Schalter A Ruhekontakt
GYPK
Schalter A Schliesskontakt
BKRD
Schalter B Eingang
BKBU
Schalter B Ruhekontakt
BKPK
Schalter B Schliesskontakt
WHRD
Potentiometer 0...100 % (P1-P2)
WHBU
Potentiometer Abgriff
WHPK
Potentiometer 100...0 % (P3-P2)
Meaning
Abbreviation
RD
System potential AC 24 V
BK
System neutral
VT
Actuating signal AC 0 V "clockwise"
OG
Actuating signal AC 0 V "anticlockwise"
GY
Actuating signal DC 0...10 V, 0...35 V
PK
Position indication DC 0...10 V
BU
Neutral
BK
Actuating signal AC 230 V, "clockwise"
WH
Actuating signal AC 230 V, "anticlockwise"
GYRD
Switch A input
GYBU
Switch A normally closed contact
GYPK
Switch A normally open contact
BKRD
Switch B input
BKBU
Switch B normally closed contact
BKPK
Switch B normally open contact
WHRD
Potentiometer 0...100 % (P1-P2)
WHBU
Potentiometer pick-off
WHPK
Potentiometer 100...0 % (P3-P2)
M4626
ok / no!
ok
ok
ok
ok
no!
no!
no!
2023-02-08
9/12