IAQ Ranges. (AirQ Box only) Allows you to define the IAQ measurement ranges (upper and
lower).
Air quality is calculated based on a particle density of PM
by the user.
- Good (less 25 μg/m
- Medium (between 25 and 50 μg/m
- Low (from than 50 μg/m
Airtools settings in Aidoo PRO Aerothermal
Limits*. By default it is disabled. Once it is enabled, it allows you to set the maximum
temperature for heating mode and the minimum temperature for cooling mode.
* Available only if the air to water unit is configured to work with room temperature (TH).
Note: When temperature limits are enabled it will not be possible to use Auto mode.
Auto Mode (dual setpoint)**. Allows you to configure changing from automatic mode based
on the setpoints defined for the cooling and heating mode. The configurable parameters are:
Setpoint differential. Establishes the minimum differential between cooling mode and
heating mode setpoints (by default 1 ºC / 2 ºF).
Mode switching protection (min). Allows you to define the minimum operating time
before allowing a change of mode, by default 30 min.
** Available only in air to water units that have Auto mode and that are configured to work
with room temperature (TH).
Digital input*. Allows you to activate or deactivate this function and change:
Settings. Allows you to set the input as normally open or normally closed.
a.
Activation by state: the state is persistent, if the input is activated the machine will be
forced off until it changes state.
b.
Activation by edge: the status is punctual, only the on/off is sent when the opening
or closing condition is met for the first time.
Time to turn off (minutes). Displays a drop-down for selecting the time (in minutes)
that you want to elapse before turning off the equipment after receiving the signal. If
disabled, the equipment will automatically turn off after receiving the signal.
Time to turn on (minutes). Allows you to select the time (in minutes) that must elapse
with the signal deactivated before the equipment turns on again. This setting only turns
on the equipment if it has previously been turned off. If it is disabled, the equipment
must be switched on again manually.
* In air to water units with 2 water circuits, the digital input only affects to circuit 1.
by default).
3
by default).
3
by default).
3
, which allows three levels to be set
2.5