There are 3 outside Temperature scenarios:
< T
T
Lock Heat Pump
EN
outside
T
Lock Heat Pump
T
Lock Heat Pump
Note: For units that do not have the "Outside Temperature" mode parameter, the outside
temperature provided by the Cloud will be taken as the default.
Note: The auxiliary heat and heat pump lock outside temperature difference will be at least
ΔT
= 6ºC, and priority will be given to heat pump lock temperature over auxiliary heat lock
min
temperature.
Digital input. Allows you to activate or deactivate this function and change:
Settings. Allows you to set the input as normally open or normally closed.
a.
Activation by state: the state is persistent, if the input is activated the machine will be
forced off until it changes state.
b.
Activation by edge: the status is punctual, only the on/off is sent when the opening
or closing condition is met for the first time.
Time to turn off (minutes). Displays a drop-down for selecting the time (in minutes)
that you want to elapse before turning off the equipment after receiving the signal. If
disabled, the equipment will automatically turn off after receiving the signal.
Time to turn on (minutes). Allows you to select the time (in minutes) that must elapse
with the signal deactivated before the equipment turns on again. This setting only turns
on the equipment if it has previously been turned off. If it is disabled, the equipment
must be switched on again manually.
Smart thermostat*. In the case of having a connection with a smart thermostat, this allows you
to select if the control is carried out by the Airzone Cloud app or by the thermostat in the case
of not having a link or connection with the third-party account.
* Not available in Bluetooth configuration.
Auto Mode (dual setpoint). Allows you to configure changing from automatic mode based on
the setpoints defined for the cooling and heating mode. The configurable parameters are:
Setpoint differential. Establishes the minimum differential between cooling mode and
heating mode setpoints (by default 1 ºC / 2 ºF).
Mode switching protection (min). Allows you to define the minimum operating time
before allowing a change of mode, by default 30 min.
Limits. By default it is disabled. Once it is enabled, it allows you to set the maximum
temperature for heating mode and the minimum temperature for cooling mode.
Note: When temperature limits are enabled it will not be possible to use Auto mode.
10
< T
Lock Aux.Heat
< T
< T
outside
Lock Aux.Heat
< T
< T
Lock Aux.Heat
outside
Demand
Indoor unit
ON
ON (FAN Max.)
OFF
ON (FAN Min.)
ON
ON (Set Mode)
OFF
OFF
ON
ON (Set Mode)
OFF
OFF
* Auxiliary Heat active only for Heat mode and Auto mode.
Auxiliary
Heat Pump
Heat
OFF
ON
OFF
OFF
ON
ON*
OFF
OFF
ON
OFF
OFF
OFF