gefran 1600 Manual De Uso página 26

Ocultar thumbs Ver también para 1600:
Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 66
Function of "MAN" LEDs: M/A, L/R, ATUN, IN1, IN2 repetition,
led. 1
event programmer, serial port enabled, errors present
LEd.1 (MAN), LEd.2 (AUX), LEd.3 (REM)
LEd.x Function
led. 2
0
none
1
MAN/AUTO (ON in manual, OFF in auto)
2
LOC/REM (ON in remote, OFF in local)
3
self-tuning enabled
4
autotuning enabled
led. 3
5
IN1 repetition
6
IN2 repetition
7
enable serial dialogue
8
HOLD on
9
Error present (error code <> 0)
10
Softstart running
11
SP1...SP4 - bit Lo Indication
12
SP1...SP4 - bit Hi Indication
13
Start / Stop Timer
14
Reset Timer
+ 16 for flashing LED function
• Lin
Custom linearization for main
Lin
or aux input (*)
st. 0 0
Step 0
Scale Limits
......
st. 3 2
Step 32
Scale Limits
(*) Not available for :
enabled input correction function (SenS + 8)
TC custom input type (SenS = 0; tyPE = 20, 21)
RTD custom input type (SenS = 1; tyPE = 4, 5)
PTC custom input (SEnS = 2 ; tyPE = 2, 3)
• CuSt
CuSt
Set custom "dAtA" menu
Set number of parameters
xead
in custom menu
[ 0 ... 14 ]
pa. 0 1
Identification code for
parameter 1
......
pa. 1 4
Identification code for
parameter 4
X X X X
The identification code is specified in this
position, under the parameter name
x
• U.CAL
U.CAL
User
U.CAL
calibration
26
Function
1
Analogue output 1
2
Analogue output 2
3
Input 1 - custom probe 10V
4
Input 1 - custom probe 50mV
5
Input 2 - potentiometer
Tabla de contenido
loading

Este manual también es adecuado para:

1800