Danfoss AK-RC 305W Manual De Instrucciones página 9

Idiomas disponibles
  • ES

Idiomas disponibles

Basic configuration
Level 1
Level 2
Description
b00
Delay of all functions on receiving power supply
b01
Cold room light timing
Function of password
b10
0=Inactive, 1=Block access to parameters, 2=Block keypad
PAS
Access code (Password)
b20
MODBUS address
bcn
Communication speed:
b21
0=9600 bps, 1=19200 bps, 2=38400 bps, 3=57600 bps
Acoustic alarm enabled: 0= No, 1=Yes
b22
Activation of manual calibration: 0=Deactivated, 1=Activated
b30
Requires security code, see page 6.
Unt
Work units: 0=°C, 1=°F
EP
Exit to level 1
Inputs and outputs
Level 1
Level 2
Description
Connected probes
I00
1=Probe 1 (Cold room), 2=Probe 1 (Cold room) + Probe 2 (Evaporator)
Configuration of digital input 1
0= Deactivated, 1=Door contact, 2=External alarm,
I10
1)
3=Severe external alarm, 4=Change of SP, 5=Remote defrost,
6=Defrost block, 7= Low pressure switch, 8=Remote Stand-by
Polarity of the digital input 1
I11
0=Activates on closing contact; 1=Activates on opening contact
Configuration of digital input 2
0= Deactivated, 1=Door contact, 2=External alarm,
3=Severe external alarm, 4=Change of SP, 5=Remote defrost,
I20
6=Defrost block, 7=Register probe, 8=Probe 2° evaporator
In0
9=High pressure switch for Hot Gas, 10=2nd cold room temperature probe,
11=Product temperature, 12=Remote Stand-by
Polarity of the digital input 2
I21
0=Activates on closing contact; 1=Activates on opening contact
Configuration of relay AUX1
o00
1)
0=Deactivated, 1=Compressor/Resistor sump, 2=Light, 3=Virtual control
Configuration of relay AUX2
0=Deactivated, 1=Alarm, 2=Light, 3=Virtual control,
o10
4=Door frame resistance, 5=Defrost 2° evaporator,
6=Same as solenoid status, 7=Same as unit status, 8=Drainage resistor
EP
Exit to level 1
* According to wizard.
1)
It can only be modified using the configuration wizard (InI).
2)
Option not available in AK-RC 305W
HACCP alarm
Level 1
Level 2
Description
h1
Maximum temperature of HACCP alarm
HCP
h2
Maximum permitted time for activation of the HACCP alarm (0=Disabled)
EP
Exit to level 1
© Danfoss | Climate Solutions | 2022.07
Values
Min.
Min.
bps
Values
2)
,
Values
°C/°F
H.
Min.
Def.
Max.
0
0
255
0
0
999
0
0
2
0
0
99
1
1
247
0
0
3
0
1
1
0
0
1
0
1
1
Min.
Def.
Max.
1
2
2
0
*
8
0
*
1
0
0
12
0
0
1
0
*
3
0
2
8
Min.
Def.
Max.
-50
99
99
0
0
255
AN41504517847601-000101 | 9
loading