Pentair Flotec FPCC5030 Manual De Instalación Y Funcionamiento página 5

Sistema de batería auxiliar
Idiomas disponibles

Idiomas disponibles

INTERNET AND ALERTS CONFIGURATION
INTERNET CONNECTION AND ALERTS CONFIGURATION
Before setting up the Virtual Water Assistant (VWA), make sure
your Battery Backup Unit is installed correctly, refer to Owner's
Manual for instruction.
Make sure the primary pump and battery backup unit has
power. Verify the system is operational by pressing the 'Test
System' button and observing the test sequence.
1.
Download the Pentair Home app to your mobile device
from the App Store® or Google Play™ Store.
2.
Open the app.
EXISTING USERS: LOGIN to your account.
NEW USERS: Scroll down in the App and click SIGN
UP.
3.
Enter a valid EMAIL and PASSWORD.
4.
Select TERMS OF SERVICE.
5.
Click CREATE AN ACCOUNT.
6.
Complete instruction in the VERIFICATION EMAIL
7.
LOGIN to your account.
8.
Register your device using the Unique Device ID Key
included on the device and your manual cover.
9.
The Alerts will use the e-mail(s) and phone number(s)
entered here.
10. Find an open network connection on your internet router
or other hard-wired connection. Rotate the antennae up
on the gateway.
Note: We recommend the use of an uninterrupted power
supply for your internet modem, home router and the
gateway power supply.
Router
FP983 (06-08-20)
Gateway
11. Using the supplied 1 meter Ethernet cable (or longer cable
if necessary), connect the gateway to an open network
port.
12. Connect the gateway power supply to a 115 VAC outlet, plug
into the back of the gateway.
The LED will blink red for a few seconds.
When the LED becomes solid green or solid green
with an occasional blink your gateway is connected
to the VWA servers. If not, refer to Gateway
Troubleshooting.
13. Once the gateway LED is green, go to the BBU and verify
that the AC power LED is solid green. If not, the gateway
will have to be moved closer to the BBU.
14. Test installation by clicking the "Test" icon on the web page
and verify the unit has run the test.
15. Alerts can be tested by activating the pump with the float
switch.