3.3

Fastening actuator on the valve

Actuator should be secured directly to the valve using proper bolts or via a
proper interface.
After assembly, the actuator can operate in any position.
However:
do not handle the actuator by handwheel to avoid damage on actuator
gearing.
cable glands must not be oriented upwards (loss of water tightness).
It is recommended not to position motor downwards.
4

ELECTRICAL COMMISSIONING

Ensure power wires are not supplied with electric power before wiring is
finished and the control compartment is closed.
!
If you need to open control compartment, previously cut off power supply to
the actuator.
4.1

Components (with cover open)

4
5
6
7
8
9
Actuator and its components are wired to internal terminal blocks.
1
9 – Cable entry plugs
8 – Ground terminal
7 – Heating resistor
6 – Terminal blocks
2
5 – Torque limiter
4 – Capacitor
3 – Modular reduction
gear
2 - End position cams
3
1 - Position indicator