RECEPTACLES
CAUTION
Receptacles may be marked with rating value greater
than generator output capacity.
•NEVER attempt to power a device requiring more
amperage than generator or receptacle can supply.
•DO NOT overload the generator. See "Don't
Overload Generator".
1. Digital Hour Meter Displayer
The Hour Meter indicates the per running time & total
running time. Push the button at the lower right corner
could switch each parameter easily.
2. Voltmeter Displayer
The Voltmeter indicates the voltage while at running.
3. Amperage Meter Displayer
The Amperage Meter indicates the current while at
running.
www.ducsonpower.com
Circuit Breaker
The Circuit Breaker is rated at 45A.
220V AC, 30A/50A Receptacle and Three Phase
Connection Poles
Use a compatible three prong plug with this
receptacle (Figure 4). Connect a 3-wire cord, set rated
220V at 30 AC Amps to the plug. For Single phase,
the receptacle power 220V AC, 30 Amps, 50Hz Loads
requiring up to 6.6KVA. Total output for three
receptacles require 10KVA. For Three Phase, the
receptacle power 220V AC, 30Amps, 50Hz loads
requiring up to 3.3KVA. The Three Phase loads
requiring 12KVA stable output, if the power factor
goes to 0.8.
Figure 4 - 220 Volt AC, 30 Amp Receptacle
COLD WEATHER OPERATION
Under certain weather conditions (temperatures
below 40 F [4°C] combined with high humidity), your
generator may experience icing of the carburetor
and/or the crankcase breather system. To reduce this
problem, you need to perform the following:
1. Make sure generator has clean, fresh petrol.
2. Open petrol valve (turn valve to open position).
3. Use SAE SW-30 oil (synthetic preferred
4. Check oil level daily or after every eight (8) hours of
operation.
5. Maintain generator following "Maintenance Schedule"
in Service Center.
6. Shelter unit from elements.
7