Overcurrent AC input current too
high
Emergency stop
EPO error
button is pressed
Leading
Leakage current
(ground leakage)
error
too high
NE fault
Grounding incorrect
or connection faulty
Immediately switch off the overcurrent
circuit breaker in the distribution cabinet.
It is necessary to check if there is a low
resistance connection between two AC
output wires.
After this error has been corrected, the
Wallbox can be switched on again. If the
error persists, please contact the dealer.
Reset the emergency stop button on the
right side of the Wallbox.
Immediately switch off the overcurrent
circuit breaker in the distribution cabinet.
Check whether the AC output devices are
interrupted or there is a low resistance
connection to earth.
After this fault has been corrected, the
Wallbox can be switched on again. If the
error persists, please contact the dealer.
Immediately switch off the overcurrent
circuit breaker in the distribution cabinet.
It must be checked whether the AC wiring
is working properly.
After this error has been corrected, the
Wallbox can be switched on again. If the
error persists, please contact the dealer.