Proline Cubemass 100
Safety
instructions:
General
Safety
instructions:
Installation
Endress+Hauser
• Staff must meet the following conditions for mounting, electrical
installation, commissioning and maintenance of the device:
• Be suitably qualified for their role and the tasks they perform
• Be trained in explosion protection
• Be familiar with national regulations or guidelines
(e.g. IEC/EN 60079-14 )
• Install the device according to the manufacturer' s instructions and
national regulations.
• Do not operate the device outside the specified electrical, thermal and
mechanical parameters.
• Only use the device in media to which the wetted materials have
sufficient durability.
• Refer to the temperature tables for the relationship between the
permitted ambient temperature for the sensor and/or transmitter,
depending on the range of application, and the temperature classes.
• Alterations to the device can affect the explosion protection and must
be carried out by staff authorized to perform such work by
Endress+Hauser.
• Observe all the technical data of the device (see nameplate).
• Avoid electrostatic charge (e.g. caused by friction, cleaning,
maintenance, strong currents in the medium):
On the attached stainless steel nameplate and on painted metallic
housings that are not integrated into the local potential equalization
system.
• In potentially explosive atmospheres: Do not connect or disconnect
the electrical connection of the power supply circuit when energized.
• Only use certified cable entries and connection plugs M12×1 suitable
for the application. Please comply with the selection criteria as
defined in IEC/EN 60079-14.
• Continuous service temperature of the connecting cable:
–40 to +80 °C; however, at least in accordance with the range of
service temperature taking into account additional influences of the
process conditions (T
• Seal unused entry glands with approved sealing plugs that correspond
to the type of protection. The plastic transport sealing plug does not
meet this requirement and must therefore be replaced during
installation.
and T
+ 20 K).
a,min
a,max
XA01143D
9