INDOOR UNIT
1(L) 2(N)
S
NOTE: The cographs are for explanation
purpose only. Your machine may be
slightly di erent. The actual shape shall
prevail.
Outdoor Unit Wiring
WARNING
Before performing any electrical or wiring
work, turn o the main power to the
system.
1. Prepare the cable for connection
a. You must rst choose the right cable
size. Be sure to use H07RN-F cables.
Minimum Cross-Sectional Area of
Power and Signal Cables (For reference)
Rated Current of
Appliance (A)
> 3 and ≤ 6
> 6 and ≤ 10
> 10 and ≤ 16
> 16 and ≤ 25
> 25 and ≤ 32
> 32 and ≤ 40
b. Using wire strippers, strip the rubber
jacketfrom both ends of the signal cable
to reveal approximately 15cm (5.9") of
wire.
c. Strip the insulation from the ends.
d.
Using a wire crimper, crimp u-lugs on the
ends.
OUTDOOR UNIT
2(N)
S
L
1(L)
N
230 Vac
50 Hz
Nominal Cross-Sectional
Area (mm²)
0.75
1
1.5
2.5
4
6
NOTE: When connecting the wires, strictly
follow the wiring diagram found inside the
electrical box cover.
2. Remove the electric cover of the outdoor unit.
If there is no cover on the outdoor unit, take
o the bolts from the maintenance board
and remove the protection board.
3. Connect the u-lugs to the terminals
Match the wire colors/labels with the labels
on the terminal block. Firmly screw the u-lug
of each wire to its corresponding terminal.
4. Clamp down the cable with the cable clamp.
5. Insulate unused wires with electrical tape.
Keep them away from any electrical or metal
parts.
6. Reinstall the cover of the electric control box.
83