Settings and use of the transmitter

Configuration

It is possible to configure the measuring ranges and the units of the transmitter via switch and/or software.
To configure the transmitter, it must not be energized. Then, you can make the settings required,
with the DIP switches (as shown on the drawing below). When the transmitter is configured, you
can power it up.
Configuration
To configure the transmitter, unscrew the 4 screws from the housing then open it. DIP switches allowing
by switch
the different settings are then accessible.
Please follow carefully the
combinations beside with the DIP
switch. If the combination is wrongly
done,
the
following
will appear on the display of the
transmitter "CONF ERROR". In that
case, you will have to unplug the
transmitter, place the DIP switches
correctly, and then power the
transmitter up.
Unit settings
To set a measurement unit in air velocity and temperature, put the on-off switch 4 of the units as shown in the table
beside.
Air velocity
Temperature
Combinations
Outputs setting
To set a measuring range, put the on-off switches 1, 2 and 3 as shown beside.
Configurations of air
From 0 to 5 m/s
velocity
(Switch 1)
Configurations of
From 0 to +50 °C
temperature
(Switch 2)
Combinaisons
Configuration via LCC-S software (option)
An easy and friendly configuration with the software!
You can configure your own intermediate ranges.
Example: for a 0-30 m/s transmitter, the minimum difference of the
range is 5 m/s. The instrument could be then configured from 5 to
10 m/s.
To access the configuration via software:
• Set the DIP switches as shown beside
• Connect the cable of the LCC-S to the connection of the transmitter.
The configuration of the parameters can be done either with the DIP switch or
via software (you can not combine both methods).
1
2
message
3
4
Off
On
Switch 2
(Switch 1)
(Switch 2)
1
2
3
4
From 0 to 10 m/s
From -20 to
+80 °C
1
1
2
2
3
3
4
4
On-off switch
1
Temperature
2
measuring range
setting
3
Temperature unit
4
setting
Off
Switch 1
m/s
fpm
°C
°F
1
2
3
4
From 0 to 15 m/s
From 0 to 20 m/s
From -50 to
From 0 to 100 °C
+50 °C
1
1
2
2
3
3
4
4
Configuration
via PC
1
2
3
4
Switch 1
On-off switch
Air velocity
measuring range
setting
Air velocity unit
setting
On
From 0 to
30 m/s
From 0 to 200 °C
1
2
3
4
Please refer to the user
manual of the LCC-S to
make the configuration.