ETI SHT-4 Manual De Instrucciones página 18

Tabla de contenido
ETI Elektroelement, d.o.o.,
Obrezija 5,
SI-1411 Izlake, Slovenia
Tel.: +386 (0)3 56 57 570,
Fax: +386 (0)3 56 74 077
Web: www.eti.si
Characteristics
The SHT-4 astronomic timer is used for the automatic real-time controlling of appliances. The timer
operates all year round without the need of continuous maintenance, with minimum operating costs and
maximum savings of electrical energy. (For example for turning on heating, pumps, ventilators, public
lighting etc.). Appliances can be controlled in regular time cycles or based on a pre-set programme.
The astronomic timer does not include any optical sensors or other external equipment. After installation, it
requires no special operation or maintenance. In the case of a power supply interruption, the timer retains all
set values required for its reliable activation after power is restored.
The operation of the astronomic timer is based on the variations in the sunset and sunrise times
throughout the year. Based on the current date (internal real-time clock), it automatically modifi es
the times for turning on or off e.g. public lighting. Time updates are resolved automatically for every
day of the year. Using the Off set function, it is possible to modify the times for switching on or off by
± 120 minutes. The off set is fi xed, i.e. the same for both channels each day.
- The 2-channel design (with the option of assigning separate programmes and modes to each channel)
allows controlling two independent circuits.
- Switching modes:
- Auto - automatic switching mode:
- Programme
- switching based on a programme (astro or time).
- Random
- switches randomly in a 10 - 120 minute interval.
- Holiday
- holiday mode - option of setting up a period for which the timer will be blocked, i.e. will not
switch based on the set programmes.
- Manual
- manual mode - option of controlling the individual output relays manually
- Options of the automatic switching programme:
- Astro - switches based on the time of sunset / sunrise calculated from input date and geographical
location. This time can be corrected ± 2 hours.
- Time programme - switching based on a pre-set time programme
- Memory capacity for 100 time programmes (common for both channels).
- Programming can be performed both when power is on or in backup mode.
- Output relays only operate with a supply voltage of AC 230 V.
- Menu display selection - CZ / SK / EN / ES / PL / HU / RU (default factory setting EN).
- Selection of automatic switching between summer / winter timebased on location.
- Setting the geographic location (selection from predefi ned options).
- Exact calculation of sunrise and sunset by entering the date, time, latitude and longitude and time
zone.
- Backlit LCD display.
- Simple and easy setup using 4 control buttons.
- Sealable transparent cover on the front panel.
- The timer has a backup battery that preserves data in case of a power supply failure (reserve backup
time up to 3 years).
- Supply voltage: AC 230 V.
- 2-module, mounted onto a DIN rail, clamping terminals.
- After plugging the timer in for the fi rst time, the current time, date and geographic location must be
set for correct operation of the astronomical clock.
Symbol
A1
16
18 26 28
A2
15
25
cos φ ≥ 0.95
Type of load
AC1
Mat. contacts AgSnO
,
2
contact 16A
250V / 16A
Type of load
AC13
Mat. contacts AgSnO
,
2
contact 16A
x
Connection
A1 16 15 18
Un
A2 26 25 28
M
M
AC2
AC3
uncompensated
250V / 5A
250V / 3A
230V / 3A (690VA)
K
AC14
AC15
250V / 6A
250V / 6A
SHT-4
Timer with an astronomical program
Description
1
2
3
4
5
1. Supply voltage terminal (A1)
2. Display with back-light
3. Place for seal
4. Plug-in module
5. Supply voltage terminal (A2)
6. Output - channel 1 (16-15-18)
7. Control buttons
8. Output - channel 2 (26-25-28)
9. Indicates the day in the week
10. Indication (1st channel)
11. Indication (2nd channel)
CONTROL OF A DISPLAY WITH BACKLIGHT
Power on: Display is illuminated with a backlight for 10 seconds from the last button press.
The display continuously shows the settings - date, time, day of the week, contact state and
programme. Permanent on / off is activated by simultaneous presses of the MAN, ESC, OK
buttons. After activating the permanent on/off , the display will fl ash briefl y.
Backup mode: After 2 minutes, the display switches to the sleep mode, i.e. shows no information.
The display can be activated by pressing any button.
Mode precendence
Mode precedence
mode with the highest priority
astro and Time Program can work at the same time on a single channel.
AC5a
AC5a
compensated
230V / 3A (690VA)
to max. input C=14uF
M
DC3
DC1
24V / 3A
24V / 10A
1/5
6
9
10
11
12
13
7
SHT-4
14
15
16
8
12. Indication of date / setting menu
13. Time display
14. Control button PRG / +
15. Reset
16. Control button MAN1 / -
17. Operating modes indication
18. 12/24 hours format / sunset - sunrise
19. Indication of the switch program
20. Control button MAN2 / ESC
21. Control button OK
Display

ON / OFF

ON / OFF
ON / OFF
astro
HAL.230V
AC5b
AC6a
1000W
x
250V / 3A
M
DC5
DC12
24V / 2A
24V / 6A
EN
17
Auto + t
Prog
Man
18
19
20
21
Output mode
manual control
holiday mode
Prog
time program
.
astro
astro
AC7b
AC12
x
DC13
DC14
24V / 2A
x
Tabla de contenido
loading

Productos relacionados para ETI SHT-4

Tabla de contenido