Quick Start Guide
English
Operating temperature, protection of the instruments and information about storage
Conditions of use (°C/%RH/m): from -10 to +50 °C; in non-condensing conditions. From 0 to 2000 m.
Protection: IP65
Storage temperature: from -10 to +70 °C.
Dimensions
46 mm
90 mm
Symbols used
For your safety and in order to avoid any damage of the device, please follow the procedure described in
this document and read carefully the notes preceded by the following symbol:
The following symbol will also be used in this document, please read carefully the information notes
indicated after this symbol:
Connections
1. Active switch
2. Inactive switch
3. LCC-S software
connection
2
4. Power supply and
output signal
5. Cable gland
Inside the front housing
Light transmitter
LR 110 light sensor has a measuring range from
0 to 10,000 lux.
26 mm
1
3
Removable front face
Fixed back housing
Electrical connections – as per NFC15-100 standard
Vdc
+
-
ILUX
Settings and use of the transmitter
Configuration
To configure the transmitter, unscrew the 4 screws of the housing then open it. DIP switches allowing the different
settings are accessible.
Measuring unit setting – Active switch
To set the unit of measurement, put the on-
off switches 3 and 4 as shown in the table:
Configuration via LCC-S software (optional)
An easy and friendly configuration with the software!
To access to the configuration via software:
- Set the switch as shown below.
- Connect the cable of the LCC-S to the connection of the transmitter
4
Configuration via PC
5
This connection must be made by a qualified and trained technician.
To make the connection, the transmitter must not be energized.
Power supply 16-30 Vdc
+
-
Vdc
Display/regulator/PLC
A
or
passive type
ILUX
+
2 wires
On-off switch
1
2
3
Setting of the measuring unit
4
Off
On
To configure the transmitter, it must not be energized. Then you can make the required settings
thanks to the DIP switches as shown on the drawing below. When the transmitter is configured, you
can power it up.
Configurations
Combinations
Caution: The configuration of the parameters can be done either by
DIP switch, or by software (you cannot combine both solutions).
To configure the
1
transmitter, please
2
refer to the LCC-S user
3
manual.
4
Switch 1
Display/regulator/PLC
active type
+
+
A
16-30 Vdc
-
-
2 wires
2 wires
lux
fc
1
1
2
2
3
3
4
4