Handook page
44/128
Installation Guide
Alarm Module T941AM8
T941AM8 has 8 physical inputs for connection to external alarm devices. Inputs are galvanically isolated, have
transient protection, and can be programmed for making or breaking contacts. There are an additional 56
logical inputs that can only be activated by programmed parameters.
A FLASH PROM in T941AM8 enables remote programming of the program and parameters. T941AM8 is
used in teleCOURIER 900, telePROTECT 900, and CTS 900.
T941AM8 is not intended for connection to public telephone networks.
Note:
To facilitate service after the unit is installed,
we recommend a free space of about 50 mm
above and 150 mm below the unit.
1
1995 08 31
Installation Guide - Alarm Module T941AM8
Dimensions (H x W x D)
275 x 130 x 60 mm
56,5
112
9
9
275
188,5
65
130
2
1
1. General
As a complement to this installation guide, see also
the "System Installation" document for the respective
system :
teleCOURIER 900, doc. no. TD 90227GB,
telePROTECT 900, doc. no. TD 90678GB, or
CTS 900, doc. no. TD 90795GB.
Supply voltage:
12,5 Vdc ± 10%
Current
150 mA max
consumption:
+ 100 mA max for all inputs.
For selection of input connection
see point 9.
Delivery includes:
• T941AM8
• Modular bus cabling
• If T941AM8 is to be used in a system with speech,
speech module T941SM must be mounted on the
PC board. Installation Guide TD 90648GB for
T941SM should be included in the delivery
Tools etc., required:
• Screw driver
• Screws for installation
• Soldering iron
2. Installation
The alarm module should be placed in a dry environ-
ment with a temperature range of 0 to +40ºC.
The alarm module can be connected together with
other units in the 900 system, either via modular
system bus cabling or via twisted-pairs (point 8).
To replace the PC board, see point 14.
The second drawing at left shows dimensions for
installing the alarm module.
Use a screwdriver or similar to release the cover by
applying a light pressure to the two snap catches (1)
and remove the cover (2).
TD 90858GB
1