Settings
Select the site your Aidoo Fancoil belongs to in the Airtools menu and choose the MAC address
of the device to be configured. The following settings are available:
General parameters
•
Installation type. You can configure a 2-pipe (default) or 4-pipe installation.
•
Automatic mode change depending on battery temperature (2-pipe installation). Only
available if the AI2 battery temperature probe is installed (see fan Auto Mode for more
information).
•
Dehumidifier function. Only available if the cooling battery temperature probe is installed
and the battery temperature is less than 10°C. This function allows you to automatically
switch to dry mode when the installation is working in cooling mode and the set
dehumidification conditions are reached.
•
Steady ventilation. This parameter can be used to configure the behavior of the fan when
comfort is reached, independently for cooling and heating mode.
•
V minimum and V maximum (DC fan voltage). These system functions allow fan speeds to
be adjusted according to the voltage specifications of the indoor unit manufacturer.
•
Basic mode. This allows you to activate the thermostat's basic mode. It is activated by
default. The parameters that can be controlled in basic mode are: On/Off, Set-point
temperature and Fan speed.
•
Cooling mode/Heating mode:
Lowest temp. /Highest temp. These allow you to select the maximum temperature for
heating mode (19-30°C, by default: 30°C) and the minimum temperature for cooling mode
(18-26°C, by default: 18°C), in steps of 1°C. If you want, you can disable any of the modes.
Cooling battery temperature/Heating battery temperature. These allow you to configure the
temperature limit values of the cooling and heating batteries if they are installed on output
AI2 (2-pipe installation) or AI2 and AI3 (4-pipe installation). They will be used as a reference
for automatic mode changeover, fan management and control of the minimum opening of
the proportional valves.
a.
Heating battery. This sets the minimum temperature for the water in the heating battery
(by default, 37°C).
b.
Cooling battery. This sets the maximum temperature for the water in the cooling battery