INTRODUCTION & SPECIFICATIONS
Congratulations and thank you for your purchase of a control panel utilizing the Installer Friendly
Series ® controller. This manual explains the features and operations of the controller which
was designed to operate up to two pumps for tank pump down applications. The controller
automatically controls the operation of the pump(s) based on the status of float switches or
C-Level™ sensor .
GENERAL
•
One or two pump level controller
•
Operates using float switches or C-Level™
sensor
•
HMI - Rotary selector for menu navigation
and editing settings
•
HMI - High-Brightness 2.4" color graphic LCD
display, 240X320 pixel resolution
PUMP CONTROL AND PROTECTION
•
Automatic pump alternation (duplex)
•
Multiple alternation configurations
•
Automatic alternation on pump fault
•
Pump run indication
•
1-2 Pump power relays, 240 Vac, 20A max.
SYSTEM
•
Alarm counts
•
Pump cycle counts
•
Pump run time
ELECTRICAL SPECIFICATIONS
•
Universal 85-265 Vac, 50/60Hz
Control/Alarm power input
•
0-250 Vac, 50/60Hz, 20A max. Pump Power
input
•
5kA short circuit current rating
•
Auxiliary Power -- 24 Vdc, 100mA max. class 2
SJE Rhombus
®
DEDICATED I/Os
•
4 Float switch inputs
•
C-Level™ sensor with 2 backup floats
•
1 Auxiliary alarm input
•
2 Pump OL/thermal cutout inputs
•
1 Test/Silence/Manual alarm reset input
•
1 Alarm beacon output, 24 Vdc, 60mA max.
•
1 Alarm horn output, 24 Vdc, 30mA max.
COMMUNICATION
•
Dedicated display communication port
(RJ45), RS485, Modbus protocol.
•
Expansion communication port (RJ45),
RS485, Modbus protocol
ENVIRONMENT
•
Operational temperature -20ºF to 122ºF
(-30ºC to 50ºC)
•
Storage temperature -40ºF to 140ºF
(-40ºC to 60ºC)
•
Relative Humidity (RH) 5% to 95%
(non-condensing)
•
Indoor rated - for indoor use or mounted inside
of an outdoor rated enclosure
E2
Type IFS Operation Manual