ALARMS

ALARM TEXT
High Level C-Level™
High Level Float
Redundant Off Alarm
Comm Fault
Expansion Port Fault
P1 Overload
P1 Seal Fail
P1 Thermal Cutout
P1 Fault
P2 Overload
P2 Seal Fail
P2 Thermal Cutout
P2 Fault
Float Fail
SJE Rhombus
®
DEFINITION
Tank level has risen above the high
alarm level setpoint.
Tank level has risen above the high
water float switch level.
Tank level has fallen below the
redundant off float switch level.
(Redundant off alarm activation
must be enabled - C-Level™ sensor
configurations only)
The display has lost communication
connection with the controller.
The controller has lost communication
connection with the expansion
modules.
The controller has sensed an open
circuit on the Pump 1 OL/Thermal input
terminals.
The seal fail module has sensed a seal
leak condition in Pump 1, based on the
seal fail setting.
The controller has sensed a change
in the status of the Pump 1 thermal
input on the Seal Fail/Thermal Cutout
expansion module.
The controller has operated in lag mode
for three consecutive cycles while
Pump 1 was lead pump.
The controller has sensed an open
circuit on the Pump 2 OL/Thermal input
terminals.
The seal fail module has sensed a seal
leak condition in Pump 2, based on the
seal fail setting.
The controller has sensed a change
in the status of the Pump 2 thermal
input on the Seal Fail/Thermal Cutout
expansion module.
The controller has operated in lag mode
for three consecutive cycles while
Pump 2 was lead pump.
The controller has sensed a float
switch closure that is outside of the
normal sequence of operation.
E12
FIX
• Ensure pumps are operating normally.
• Ensure discharge pipe is intact.
• Ensure the high alarm level setpoint is
set above the normal operating level.
• Ensure pumps are operating normally.
• Ensure discharge pipe is intact.
• Ensure the high water float switch has
been installed above the normal
operating level.
• Ensure pumps are operating normally.
• Ensure there are no leaks in the tank.
• Ensure the redundant off float switch
has been installed below all other floats
or sensor setpoint levels.
• Ensure display cable is properly
connected to the display and controller.
• Ensure expansion module cable is
properly connected to the controller.
• Ensure Pump 1 motor overload relay or
thermal cutout is functioning correctly.
• Ensure Pump 1 motor is functioning
correctly.
• Service Pump 1 seal.
• Ensure Pump 1 motor thermal cutout is
functioning correctly.
• Ensure Pump 1 motor is functioning
correctly.
• Ensure Pump 1 is operating normally.
• Ensure the discharge pipe for Pump 1 is
intact.
• Ensure Pump 2 motor overload relay or
thermal cutout is functioning correctly.
• Ensure Pump 2 motor is functioning
correctly.
• Service Pump 2 seal.
• Ensure Pump 2 motor thermal cutout is
functioning correctly.
• Ensure Pump 2 motor is functioning
correctly.
• Ensure Pump 2 is operating normally.
• Ensure the discharge pipe for Pump 2 is
intact.
• Ensure the float switches have been
installed in the proper order.
• Ensure the float switches do not
contact the sides of the tank, or
objects in the tank.