7. Installation, Fig. A ... F
Danger of short-circuits, unit
NOTICE
damage Water will penetrate if
the power cable is incorrectly
fed into the housing or if the
self-sealing grommet is not
fitted correctly.
The degree of protection is only
guaranteed if the cables are fed
through correctly at the intended
housing seal (self-sealing
grommet).
Drill a circular hole into the self-
sealing grommet [11] that is
somewhat smaller than the cable
diameter.
Danger of injury due to cuts
caused by glass breakage, if
the windowpane is under
DANGER
stress.
Only install the windowpane so
that the glass is not under stress.
If necessary, remove the
windowpane and re-fit it so that it
is not under stress.
Shutter does not close
NOTICE
properly, if it is tensely
installed.
Only mount the shutter on a
level surface in order to
guarantee the shutter function.
Notes
● Make sure there is sufficient space to
the window frame, wall or ceiling.
● Never dismantle the shutter.
Fig. A: Installation preparation
1. Lay the power cable.
2. Get an expert to make the window cut-out
[S]. Drill the cut-out [S] in the case of wall /
wooden panel installation.
3. Clean the windowpane thoroughly before
adhesively bonding the shutter on.
Fig. B: Disassembling the inner parts
1. To do this, hold the internal housing [3]
firmly at the side and pull the connecting
flange [2] at the motor out of the cover.
2. Remove the terminal box cover [4].
In the case of wall/wooden panel installation
3. If necessary drill through the connecting
flange [2] on the 2 knockout points [X]
( Fig. B).
4. Drill through the 4 knockout points [Y]
( Fig. B1) on the shutter, with the
lamellae open.
Fig. C/Fig. C1: Installing the shutter [1]
(outside).
1. Insert the screws [5] into the eyes of the
shutter until they snap into place.
2. Remove the protective foil from the gluing
points [7].
3. Align the shutter in the window cut-out and
press it onto the pane.
In the case of wall/wooden panel installation
4. Attach the shutter [1] to the wall or wooden
panel with suitable mounting material.
Fig. D: Installing the inner parts (inside)
Danger of injury due to cuts
caused by glass breakage, if
the nuts have been over-
CAUTION
tightened.
Tighten the lock nuts [8] carefully
making sure not to over-tighten
them.
1. Attach the connecting flange [2] to the
screws [5], align it and press it gently
against the windowpane.
2. Tighten the lock nuts [8] with the supplied
socket spanner [9] ( Figs. D1 and D2).
In the case of wall/wooden panel installation
3. Attach the connecting flange [2] to the wall
or wooden panel with suitable mounting
material.
7. Installation │ gb