assing the corresponding Set Point'X' to the measurement through pressing "YES".
Select the Type for the setpoint.
The type of the setpoint can be "High", "Low", "Between", "Outside" or "Off". an
"Outside" setpoint will cause an alarm condition whenever the measurement goes
above its high limit or below its low limit. a "Between" setpoint will cause an alarm
condition to occur whenever the measurement is between its high and low limits.
h
NOTE:
If the type of set point is not "Off" additional settings can be done.
See the following description.
according to the selected type of set point, value(s) according to the limit(s) can
be entered.
Select the desired relay that will be activated if the defined conditions are reached
through the parameter SP Relay. If the chosen relay is used for another task, the
transmitter shows a message on the screen that there is a Relay Conflict.
To escape the menu of the settings for Guided Setup press p. To return to the Menu
Screen press H. The M800 will bring up the "SavE CHanGES" dialog.